Toshiba Tosvert RS485 User Manual

Page 66

Advertising
background image

E6581315

65

„

Monitor parameters *These Parameters are read-only (monitor-only) parameters.

Communication No.

Current

value

Trip data held

Function

Unit

Remarks

FC00

Monitor of key data (Effective
data)

FC01

Monitor of inverter keypad data

Refer to Section

8.3.

FC90

Trip code

FC91

Alarm code

FD00

FE00

Output frequency

0.01Hz

FD01

FE01

Inverter status 1

Refer to Section

8.2.

FD02

FE02

Frequency command value

0.01Hz

FD03

FE03

Output current

0.01%

FD04

FE04

Input voltage (DC detection)

0.01%

FD05

FE05

Output voltage

0.01%

FD06

FE06

Input terminal information

FD07

FE07

Output terminal information

Refer to Section

8.2.

FE08

CPU version 1 (application)

FE10

Past trip 1 (latest)

FE11

Past trip 2

FE12

Past trip 3

FE13

Past trip 4 (earliest)

Refer to Section

8.2.

FE14

Cumulative operation time

1h

FD15

FE15

Compensated frequency

0.01Hz

FD16

FE16

Speed feedback (real time)

0.01Hz

FD17

FE17

Speed feedback (1-sec. filter)

0.01Hz

FD18

FE18

Torque

0.01%

FD19

FE19

Torque command

0.01%

FD20

FE20

Torque current

0.01%

FD21

FE21

Exciting current

0.01%

FD22

FE22

PID feedback value

0.01Hz

FD23

FE23

Motor overload factor (OL2 data)

0.01%

FD24

FE24

Inverter overload factor (OL1
data)

0.01%

FD25

FE25

Regenerative braking resistance
overload factor (OLr data)

1%

FD26

FE26

Motor load factor

1%

FD27

FE27

Inverter load factor

1%

FD28

FE28

Regenerative braking resistance
load factor

1%

FD29

FE29

Input power

0.01kW

FD30

FE30

Output power

0.01kW

FE35

RR/S4 input

0.01%

FE36

VI/II input

0.01%

FE37

RX input

0.01%

FE38

Option AI1

0.01%

FE39

Option AI2

0.01%

Refer to Section

8.2.

FD42

FE42

Inverter status 2

Refer to Section

8.2.

FE43

MON1 output (analog option 1)

FE44

MON2 output (analog option 2)

FD45

FE45

Command mode status

FD46

FE46

Frequency setting mode status

Refer to Section

8.2.

FD48

FE48

PID command

0.01Hz

FD49

FE49

Inverter status 3

Refer to Section

8.2.

Advertising
This manual is related to the following products: