Parameter data – Toshiba Tosvert RS485 User Manual

Page 63

Advertising
background image

E6581315

62

9. Parameter data

Explanation of parameters for VF-AS1 series is described here. For communication purposes, see
the parameter list on inverter's instruction manual regarding the communication number, adjustment
range and so forth.

„

Referring to the parameter list

<Example of excerpts from the inverter’s instruction manual>

Title

Communi-
cation No.

Function

Adjustment range

Minimum set-

ting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Refer-

ence

auh

-

History function

1/1

-

-

5.1

au1

0000

Automatic accelera-
tion/deceleration

0:Deselect
1:Automatic setting
2:Automatic setting (during

acceleration only)

1/1

0

Disabled

5.2

au2

0001

Automatic torque
boost

0:Deselect
1:Automatic torque boost +

auto-tuning 1

1/1

-

Disabled

5.3

acc

0009

Acceleration time
1

0.1~6000 sec.

0.1/0.1 *2

*1

Enabled

5.2

typ

0007

Factory default
setting

0: -

1:50 Hz default setting
2:60 Hz default setting
3:Factory default setting

10:Acceleration/deceleration

time setting 0.01
sec.~600.0 sec.

11:Acceleration/deceleration

time setting 0.1
sec.~6000sec.

1/1

-

Disabled

5.20

*1: Default values vary depending on the capacity.
*2: Changing the parameter  enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).

- The summary of parameter list relating to the communication is as follows.

(1) “Title” means the display on the inverter panel.

(2) “Communication number” is affixed to each parameter that is necessary for designating the parameter for com-

munication.

(3) "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written outside the

range. The data have been expressed in the decimal notation. For writing the data through the communication
function, take the minimum setting unit into consideration, and use hexadecimal system.

(4) "Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).

For example, the "minimum setup unit" of acceleration time () is 0.01, and 1 is equal to 0.01s. For setting a
data to 10 seconds, transmit 03E8h [10 0.01=1000d=03E8h] by communication.

(5) If FA09 is set to 0, the acceleration/deceleration time parameters acc, dec, f500, f501, f510,

f511

, f514, and f515 can be set in units of 0.01 sec.

Q 

Acceleration/deceleration setting time unit (FA09)

Communication No.

Function name

Unit

Adjustment range

FA09

Acceleration/deceleration time unit

0: 0.01 sec. (0.01-600.0)
1: 0.1 sec. (0.1-6000.0)