Sidewall (general) venting information, Flex venting – Temco Tool DV1400N/P User Manual

Page 12

Advertising
background image

12

Temco DV1000/1200/1400 Series

76657

T182
sealant
12/3/03 djt

MILL-P

AC

MILL-P

AC

NOTE: Apply sealant “Mill-Pac” to inner pipe and “Mill-Pac” or high
temperature silicone sealant to outer pipe. Sealant should be ap-
plied at every joint in the vent system including at the fireplace and
at the vent terminal.

T182

Fig. 13 Apply sealant at every joint in vent system.

H

12

x

T183

typical straight up

installation

12/3/03 djt

Gas Vent

Vent Cap

Lowest Discharge Opening

Roof Pitch X/12

H (Min.) - Minimum height

from roof to lowest discharge

opening

T183

Roof Pitch

H (Min.)

Flat to 6/12

12” (305 mm)

6/12 to 7/12

15” (381 mm)

Over 7/12 to 8/12

18” (457 mm)

Over 8/12 to 16/12

24” (610 mm)

Over 16/12 to 21/12

36” (914 mm)

Fig. 14 Vertical termination location.

Sidewall (General) Venting Information

Figures 15 and 16 show examples of horizontal termi-
nation arrangements using two 90° elbows (Rigid Vent).
NOTE:
1. A maximum of two 90° elbows are permitted.
2. A minimum of 10’ (3 m) vertical from base of unit is

required if two 90° elbows are used.

3. Minimum distance between elbows is 2’ (610 mm).
4. Determine the permitted range of horizontal ter-

mination arrangement by using chart above and
deducting 3’ (914 mm) from the maximum horizontal
distance for the second 90° elbow.

VO584-100

Vent Opening

2/99 djt

Vent Opening for Combustible Wall

9³⁄₄”

(248 mm)

10³⁄₄”

(273 mm)

5⁷⁄₈”

(149 mm)

4⁷⁄₈”

(124 mm)

Fireplace Hearth

Framing Detail

Opening for Noncombustible Wall

Rnd.

8” Dia.

(203 mm)

Min.

Fireplace Hearth

VO584-100

Fig. 15 Locate vent opening on wall.

33"

(838mm)

Minimu

m

53" (1346m

m)

Maximum

28' (8.5m)

2' (610mm)

Minimum

B

12" (305mm)

Minimum

A

10' (3m)

Minimum

If length "B" is increased,

length "A" must be decreased

by a corresponding amount

T184

sidewall venting

12/3/03 djt

A vent guard should be used

whenever the termination is

lower than the specified mini-

mum or as per local codes.

T184

Fig. 16 Horizontal vent run.

Flex Venting

• Flex vent shall use the spacer springs as included

every foot to ensure proper vent operation.

• The 4” x 7” flex system may be used for all sidewall

applications and vertical venting up to 35’ (10.7 m).

• Flex shall be properly supported so there are no

sags in the system. Supports must be used at least
every 24” (610 mm) on horizontal section and every
36” (914 mm) on vertical. Wire or metal stripping
may be used to support the venting.

• For 4” x 7” flex, the 7” flex has an outside diameter

of 7¹⁄₂” (191 mm) and if installed in a chase the in-
side diameter of the chase should be 9¹⁄₂” (241 mm)
minimum.