No more than (4) 90° and (2) 45° offsets are to be used
per installation. Vent terminal cap location should be in
accordance with the Venting Graph chart and the Verti-
cal Termination Location information.
1. Measure the total wall thickness. Determine whether

or not the thimble extension is needed. If the com-
bustible wall depth is over 5” (127 mm), the exten-
sion should be used. (Fig. 19)

2. Assemble wall thimble with thimble extension flange

to top. Mate thimble to wall plate with the four tabs
provided. Bend tabs over to secure. (Fig. 19)

T186

Telescope extension

12/4/03 djt

Telescope Extension

T186

Fig. 19 The telescope extension must be used if wall thick-
ness is over 5” (127 mm).

3. Install the wall thimble assembly through the framed

opening so the firestop plate is on the interior wall.
(Fig. 20) Telescope section should extend all the way
through wall.

4. Step 1: Apply Mill-Pac to 4” flue inner pipe on cap.
Step 2: Connect 4” flex flue to flue on cap with

band clamp.

Step 3: Apply silicone sealant to 7” outer pipe on

cap.

Step 4: Slide 7” outer flex over inlet and secure with

band clamp.

5. Secure vent cap terminal to exterior wall with screw

type fasteners as needed. (Fig. 21)

6. Connect corrugated side of the extension collar (7”

dia.) into the 7” dia. flex pipe. (Fig. 22) Place a small
bead of silicone around the collar approximately 1/4”
from the leading edge of the corrugation. Insert the
collar firmly into the flex pipe and secure with the
provided (7” dia.) band clamp.

7. Place a small mill-pac bead around the top edge of

the fireplace flue collar. Then, attach the flex tube
over the flue collar with a 4” dia. band clamp.

9¹⁄₂" (241mm)

10¹⁄₂"

(267mm)

T187

wall thimble

12/5/03 djt

T187

Fig. 20 Install wall thimble with firestop on interior wall.

2" (51mm)

1" (25mm)

T188

vent cap terminal

12/5/03 djt

Inside

Wall

Wall

shield

Flex

Duct

Exterior Wall

Flange at

Top

Thimble Extension

Band Clamp

Terminal

Cap

Assembly

T188

Fig. 21 Secure vent cap terminal to exterior wall.

T189

extension collar

into flex vent

12/5/03 djt

7” (178 mm)

Band Collar

4” (102 mm)

Band Clamp

and Flex Flue

7”

(178 mm)

Flex Vent

Extension Collar

T189

Fig. 22 Insert collar into flex pipe and secure with band clamp.

ATTENTION: Spacer springs must be installed when install-
ing flexible venting system.