Flex vent through the roof (vertical) applications, Vsk7 vertical flex vent kit installation – Temco Tool DV1400N/P User Manual

Page 15

Advertising
background image

15

Temco DV1000/1200/1400 Series

76657

8. To finish connections, place a small bead of silicone

to the outside of the fireplace inlet flange. Then, slide
the extension collar over the inlet flange and secure
with the three (3) screws provided.

NOTE: We recommend driving in two (2) sheet metal
screws at 180° adjacent to the gear clamp at each joint.

Flex Vent Through the Roof

(Vertical) Applications

All models are approved for:
1. Vertical venting up to 35’ (10.7 m) with 7” x 4” flex.
2. Multiple bends allowed. See section on General

Venting.

3. With each vertical installation, a VSK7MH-2 kit may

be used.

T190

ceiling install

12/5/03 djt

Room Above
Ceiling Level

Ceiling Joist

Firestop

T190

Fig. 23 Firestop at ceiling level.

T190

ceiling install

12/5/03 djt

Firestop

Attic Above Ceiling
(Uninsulated)

Attic Above Ceiling
(Insulated)

Attic Insulation

Shield

T190

Fig. 24 Attic insulation shield.

6' (1.8m)

Maximum

35' (10.7m)

Maximum

T191

thru the roof

installation

12/5/03 djt

Roof

Attic Insulation

Shield

7” (178 mm) Dia.

Joists

T191

Fig. 25 Typical through-the-roof installation.

The VSK7 Kit contains:
• Vertical Termination Cap and Storm Collar
• 4”/7” dia. x 24” Rigid Pipe (unitized)
• 7” dia. Roof Support Components
• 0/12-5/12 Flashing with Storm Collar
• Tube High Temp Sealant
• 7” dia. Inlet Ext. Collar
• Firestop
• Hardware Pack
• Instruction

VSK7 Vertical Flex Vent Kit Installation

1. Locate the fireplace.
2. Mark ceiling above unit where flex will come through.
*-REFER TO VERTICAL TERMINATION LOCATION

CHART

3. Ceiling opening should be a minimum of 9¹⁄₂” x 9¹⁄₂”

(241 x 241 mm) and framed to that size.

4. Mark opening in roof and cut a hole minimum 9¹⁄₂” x

9¹⁄₂” (241 x 241 mm) and frame to that size.

5. Place fireplace in proper location and secure to the

floor.

6. Install the firestop at the ceiling level.
7. If an attic space (insulated or not) is located above

the ceiling, the firestop should be installed to the
underside of the ceiling. The firestop maintains the
proper air-space clearance from the vent to insula-