Toshiba – Toshiba 1500 SERIES User Manual

Page 15

Advertising
background image

TOSHIBA

MODEL NUMBER

UE1A1A006C6

UE1A1A008C6

UE1A1A010C6

CAPACITY

600 VA (0.42 kW)

800 VA (0.56 kW)

1000 VA (0.7 kW)

Input

Input voltage

Single phase, 120 Vac, +10% to -30% (*)

Input frequency

45 to 65 Hz

Input capacity

600 VA

800 VA

1000 VA

Input power factor

Approximate unity (0.95 to 1.0)

Battery

Battery rated voltage

60 Vdc

Battery backup time when fully charged

12 min. at full load (**) 8 min. at full load (**)

7 min. at full load (**)

with 0.7 power factor at 77° F (25° C)

30 min. at half load (**) 20 min. at half load (**) 18 min. at half load (**)

Recharge time

Maximum 24 hrs to 100% (90% recharge after 8 hrs) (***)

Type of batteries

Sealed lead-acid

Output

Output voltage

Single-phase, 120 volts

Output voltage regulation

Within +/- 3%, steady state

Output frequency

50/60 Hz +/- 0.5% in free-running mode (line sync range +/- 1Hz)

Output voltage waveform

Computer-grade sine wave with less than 3.0% total harmonic
distortion with linear load

Rated load power factor

0.7 lagging (0.6 to 1.0)

Voltage transient characteristic

+/- 8% under 100% load step change

Rated output current (rms)

5.0A

6.7A

8.3A

Maximum output current (peak)

15.0A

20.0A

25.0A

Inverter overload capacity

150% for 30 seconds

Crest factor

3.0

Environment

Operating temperature

32 to 104° F (0 to 40° C), optimal at 77° F (25° C)

Storage temperature

-4 to 104° F (-20 to 40° C)

Operating humidity

30 to 90%, no condensation

Altitude(****)

Less than 3000 ft (1000 m) above sea level

External dimensions

8.00W x 20.38D x 10.00H in (203W x 518D x 254H mm)

Net weight

40.3 lb (18.3 kg)

40.3 lb (18.3 kg)

43.7 lb (19.8 kg)

Acoustical noise

50 dB at max. output, measured 3.3 ft (1 m) from front panel

Efficiency (ac-dc-ac)

85%

85%

87%

Switches

Bypass switch

Automatic bypass is provided when the run switch is in the stop
position, if a fault occurs, or if an overload occurs (transfer time is
approximately 4 msec)

Interfaces

IBM (TM) AS/400

LAN Manager

See section 6.0 for details.

Fault detect and input power loss

RS232 ASCII

Options

Software for unattended

computer shutdown

Contact Toshiba for details on this option

External battery pack

Contact Toshiba for details on this option

(*) Output capacity reduced when input voltage is between -15% and -30% of nominal.

(**) Battery backup time may vary depending on the operating conditions including ambient temperature at the

installation site.

(***) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is used

for battery backup.

(****) Above 3000 ft (1000 m), output capacity reduced.

4 - 1

4.1

Standard Series Specifications

4.0

Specifications