Toshiba, 0 operating the ups – Toshiba 1500 SERIES User Manual

Page 21

Advertising
background image

TOSHIBA

Output

Display Status

Explanation

During battery backup all

green lamps flash and the

red Backup lamp is lit

continuously. As the

batteries discharge, the

Battery

green lamps extinguish

Backup

from top to bottom to

indicate remaining battery

capacity (This sample

display shows battery

voltage between 75% and

90% of battery capacity).

All green lamps are off

and the red Backup lamp

Low

is lit continuously or

Battery

flashing.

During

Battery

Backup

5.0

Operating the UPS

5.4

Front Panel Layout

ON LINE (green lamp)

Lights green when the UPS’s inverter is supplying power to the load.

AC INPUT (green lamp)

Lights green when normal ac input power is being supplied to the UPS

Unit.

FAULT (red lamp)

Lights red when the UPS unit has tripped in the fault mode.

REPLACE BATTERY (red lamp)
Lights red to indicate batteries may need to be replaced.

5.5

UPS On-Line Mode Display
The following chart shows normal operating conditions when the UPS On-Line

lamp is green.

= Flashing LED

= Steady-lit LED

Output

Display Status

Explanation

When output current is

between 30% and 100%,

the green lamps light in

15% increments (from

Normal

bottom to top) to indicate

relative output value

(This sample display

shows output current at

45% to 60% of rated

current).

All the green lamps will

light and the red Overload

lamp will flash. If the load

exceeds 135% of the max.

rated output the red

Overload

Overload lamp will light

continuously.Remove

overload as quickly as

possible to prevent fault

(fault timeouts vary

depending on overload

condition).

5 - 4