TOSHIBA

5.0

Operating the UPS

5.3

Operation Monitoring

5.3.1

Visual Indicator Functions

The following LED (light emitting diode) indicators are located on the front panel

(see Section 9.2 "Panel Layout"). Refer to these lamps for visual information

about the operating condition of the UPS (see Section 5.3.3 "Visual and Audible

Indicator Function Chart").

1) AC Input: This green LED lights when normal ac input power is being

supplied to the UPS unit.

2) On Line: This green LED lights when the inverter output voltage is normal.

3) Fault: This red LED lights when an abnormal operating condition is

detected. Operation of the unit's inverter is inhibited until the fault has been

corrected and the system reset (see Section 5.10 "System Reset").

5.3.2

Audible Alarm Functions

The UPS is equipped with an audible alarm system which activates under various

operating conditions. Sound patterns are used to indicate these conditions (see

Section 5.3.3 "Visual and Audible Indicator Function Chart"). Alarms for the

battery backup mode or low battery voltage will stop automatically when AC input

voltage is restored. Alarms for a fault condition will continue to sound until the

UPS has been reset (see Section 5.10 "System Reset").

5.3.3

Visual and Audible Indicator Function Chart

5 - 3

Overcurrent (OC)

Problem in chopper or

1) "Fault" LED 1) Auto

inverter circuit.

is ON

transfer

2) "On Line"

to bypass

DC Bus Overvoltage (DCOV) DC Bus > 115% of rated.

LED is OFF 2) Chopper

3) "AC Input"

stopped

Ouput Overvoltage (OV)

V out > 110% of rated.

LED is ON

3) Inverter

stopped

Undervoltage (UV)

V out < 85% of rated.

Overheat (OH)

Heatsink exceeds 90º C.

Overload (OL)

Output current and over-

load specifications have

been exceeded.

Battery problem

Problem in battery

1) “Replace

1) Bypass or

circuit.

Battery”

On-Line

LED is ON

mode.

Normal battery backup

Loss of AC power

1) "Fault" LED 1) Chopper

operation

is OFF

running

2) "On Line"

2) Inverter

LED is ON

running

3) "AC Input"

LED is OFF

Low battery voltage

Battery voltage too low,

Shutdown imminent.

Condition

Cause

Visual

Indicators

ON

OFF

.5s .5s

2s

1.5s

ON

OFF

UPS

Operation

5s

70s

ON

OFF

1s

2s

ON

OFF

1s

.5s

ON

OFF

Audible

Alarm

Pattern