Toshiba – Toshiba 1500 SERIES User Manual

Page 25

Advertising
background image

TOSHIBA

6.0

UPS Control Interface

6.2

RS-232C Serial Communication Interface

The available data from the UPS, via RS-232C communication, is shown below:

Output voltage

Output current

Operating conditions

Battery voltage

Input frequency

Output frequency

Utility power OK

Low battery voltage detected

UPS operating status

UPS in BYPASS mode

(described as ‘yes’ or ‘no’)

UPS in NORMAL mode

Input and output frequency synchronized

UPS ‘fault’ occurred

DC bus overcurrent

DC bus overvoltage

DC bus undervoltage

'Fault’ details

Input overcurrent

(described as ‘occurred’

Overheat

or ‘not occurred’)

Overload being timed

Overload (allowable time exceeded)

Output overvoltage (during NORMAL mode)

Output undervoltage (during NORMAL mode)

6.2.1

UPS Shutdown (via RS-232C)

When the UPS is operating from its internal batteries, a ‘shutdown’ order can be

sent to the UPS telling it to turn OFF after a user-specified amount of time. This

function can allow you to stop discharging the UPS batteries after an orderly

system shutdown has been completed. The UPS can be programmed to turn

OFF up to 8 minutes after the ‘shutdown’ command is given. This command can

be cancelled before the specified time has elapsed.

6.3

Dry Contact Interface

The Dry Contact interface uses pins 16 trough 22. Pins 24 and 25 are used for the

shutdown function. The following schematic shows the contact state and pin assignments

for each signal output along with the associated DB25 connector pinout.

16 Dry Contact common

17

Notes:

Battery Backup

1) Pin “switches are shown

18

in their inactive states

(ex. if battery voltage is

19 Battery voltage “low”

low then pin 19 will be

connected to pin 16)

20 UPS “on”

2) Contacts are rated as

21 Bypass “on”

follows:

dc: 48V, 0.1A

22 Fault detect signal

ac: 30Vrms (42V-peak)

0.07A(0.1A-peak)

6 - 2

}