Owner’s manual, Fireplace installation, Continued – Vanguard Managed Solutions MBDV37 User Manual

Page 21

Advertising
background image

21

106497

OWNER’S MANUAL

FIREPLACE
INSTALLATION

Continued

Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)

1.

Close equipment shutoff valve (see Fig-
ure 43).

2.

Pressurize supply piping system by ei-
ther opening propane/LP supply tank
valve for propane/LP gas fireplace or
opening main gas valve located on or near
gas meter for natural gas fireplace, or
using compressed air.

3.

Check all joints from propane/LP sup-
ply tank or gas meter to equipment
shutoff valve (see Figure 44 for pro-
pane/LP or Figure 45 for natural). Ap-
ply commercial leak test solution to all
gas joints. Bubbles forming show a
leak. Correct all leaks at once.

Pressure Testing Fireplace Gas
Connections

1.

Open equipment shutoff valve (see
Figure 43).

2.

Open propane/LP supply tank valve for
propane/LP fireplace or main gas valve
located on or near gas meter for natu-
ral gas fireplace.

3.

Make sure control knob of fireplace is
in the OFF position.

4.

Check all joints from equipment shutoff
valve to thermostat gas valve (see Fig-
ure 44 for propane/LP or Figure 45 for
natural). Apply commercial leak test so-
lution to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.

5.

Light fireplace (see Operating Fire-
place
, pages 26 and 27). Check all other
internal joints for leaks.

6.

Turn off fireplace (see To Turn Off Gas
to Appliance
, page 26).

Figure 43 - Equipment Shutoff Valve

ON

POSITION

OFF

POSITION

Open

Closed

Equipment
Shutoff
Valve

Figure 45 - Checking Gas Joints for Natural Gas Fireplace

Figure 44 - Checking Gas Joints for Propane/LP Gas Fireplace

Propane/LP Supply
Tank

Gas Valve

Equipment
Shutoff Valve

Gas Meter

Gas Valve

Equipment
Shutoff Valve

Continued