Direct-vent fireplace, Troubleshooting, Continued – Vanguard Managed Solutions MBDV37 User Manual

Page 32

Advertising
background image

32

106497

DIRECT-VENT FIREPLACE

®

OBSERVED PROBLEM

Pilot will not light

No gas to burner, although wall switch and
valve are set to the ON position

Frequent pilot outage

Burner goes off after a short time

Burner does not light after pilot is lit

POSSIBLE CAUSE

1. No gas supply, or shutoff valve is OFF
2. Air in gas line

3. Construction debris clogging pilot orifice

4. Low gas pressure
5. Control valve knob is not on the PILOT

position

6. Kinked pilot line

7. Bad valve

8. Bad thermocouple or loose connection

1. Wall switch wires defective

1. Pilot flame may be too low, causing

safety pilot to “drop out”

1. Venting recirculation problem

1. Burner orifice clogged

2. Inlet gas pressure is too low

3. Thermopile leads disconnected or im-

properly connected

4. Thermopile is defective

REMEDY

1. Check to see if you have gas supply
2. Hold control valve in the PILOT position

for 2 to 3 minutes to purge air. If you smell
gas stop and wait for a few minutes before
trying to light the fireplace

3. Remove debris and dirt, inspect and

clean any other possible obstructions

4. Contact your gas supplier
5. Refer to section on pilot lighting

6. Have a qualified technician replace pi-

lot line

7. Replace control valve (see Replacement

Parts, page 35)

8. Tighten thermocouple or replace

1. Check electrical connections

1. Clean and adjust pilot flame for maximum

flame impingement on thermopile

1. Have a qualified technician check vent-

ing system for leaks or obstructions.
Have a qualified technician measure the
pilot’s millivoltage

1. Clean burner (see Cleaning and

Maintenance, page 28) or replace burner
orifice

2. Contact local propane/LP or natural gas

company

3. Reconnect leads (see Wiring Diagram,

page 35)

4. Replace thermopile

TROUBLESHOOTING

Continued

www.desatech.com

Advertising
This manual is related to the following products: