WHISPERKOOL SERIES ADVANCED CONTROLLER (CONT.)

Customer

Preference

Selection

Menu

(cont.)

CON/COF — Compressor on time (CON) and off time (COF) with a Probe 1 failure alarm:

These parameters are set at CON 40 minutes and COF 10 minutes. In the event that there

is a Probe 1 failure alarm, the compressor /refrigeration system automatically starts a

predetermined ON/OFF cycle, which is controlled by the CON and the COF parameters.

The customer can adjust these parameters to maintain the desired bottle probe tempera-

ture. During a Probe 1 failure alarm, the bottle probe temperature can be monitored by

pressing the “Up” or “Down” arrow to view the temperature history.

HES — Differential for Energy Reduction: This parameter is set at 4, which results in a set

point of 58°F during energy reduction. A decrease in this setting will decrease the set point,

and an increase in this feature will increase the set point.

ALARM CODES

Message

Cause

Output

“P1”

Room probe failure

Toggle “Con” and “COF” depending

on your temperature needs, if

necessary, or replace room probe

“P2”

Evaporator probe failure

Defrost end is timed

“HA”

High temperature alarm

Outputs unchanged

“LA”

Low temperature alarm

Outputs unchanged

“EA”

External alarm

Outputs unchanged