Wiring diagrams – White Rodgers 1F85CA-0471 User Manual

Page 3

Advertising
background image

3

WIRING DIAGRAMS

Heat Pump Connections
If you do not have a heat pump system, refer to fi gures 4-6.
Refer to equipment manufacturers’ instructions for specifi c
system wiring information.
You can confi gure the thermostat for use with the following
heat pump systems.

Figure 3 – Heat Pump Systems

HEAT PUMP TYPE 1 (HP 1). Single stage compressor
system; gas or electric backup.
HEAT PUMP TYPE 2 (HP 2). Multi-stage compressor or two
compressor system with gas or electric backup.
After wiring, see INSTALLER CONFIGURATION section for
proper thermostat confi guration.

NOTE: If your system does

not provide an E connection,

jumper W2 to W/E to use

the Auxiliary Heat in the

Emergency Mode.

* Common connection

required for fault or

malfunction indication.

Heat Pump 2

(HP2)

Heat Pump 1

(HP1)

O

Energized in

Cool Mode

B

Energized in

Heat, Off,

Emergency

Mode

2nd

Stage

(Com-

pressor)

No

Output

Heat and

Cool Mode

1st Stage

(Compressor)

Blower/

Circulator

Fan Energized

on Call for

Heat or Cool.

Set Elect/Gas

Option for

Emergency

Mode

Heat Mode
2nd Stage.

Emergency

Mode 2nd

Stage

Heat Mode

3rd Stage.

Emergency

Mode 2nd

Stage

Emergency

Mode

1st Stage

Optional*

24 Volt

(Com-

mon)

Fault Indicator

or System

Malfunction

Switch

24 Volt

(Hot)

Cool

System

Y

W/E

C

L

RC

CLASS II

TRANSFORMER

HOT

24VAC

NEUTRAL

120VAC

24 Volt

(Hot)
Heat

RH

Jumper

Y2

W2

G

Jumper

Comfort Alert II Module

or Similar System

Malfunction Module

O/B

Single Stage and Multi-Stage Connections
Refer to equipment manufacturers’ instructions for specifi c
system wiring information.
This thermostat is designed to operate a single-transformer
or two-transformer system.
You can confi gure the thermostat for use with the following
fossil fuel systems:

SINGLE STAGE (SS 1) gas, oil or electric.
MULTI-STAGE (MS 2) gas, oil or electric.
After wiring, see INSTALLER CONFIGURATION section for
proper thermostat confi guration.

Figure 4 – Single Stage or Multi-Stage System (No Heat Pump) with Single Transformer

* Common connection

required for fault or

malfunction indication.

Single

Stage 1

(SS1)

Multi-

Stage 2

(MS2)

O

Energized Constantly

in Cool Mode

B

Energized Constantly

in Heat, Off,

Emergency

Mode

No

Output

Cool

Mode

2nd

Stage

Cool Mode

1st Stage

Blower/

Circulator

Fan Energized

on Call for

Cool (and

Heat if

configured
for Electric

Heat)

No Output

Heat Mode

2nd Stage

Heat

Mode

1st Stage

Optional*

24 Volt

(Com-

mon)

24 Volt

(Hot)

Cool

System

Y

G

W/E

C

L

RC

CLASS II

TRANSFORMER

HOT

24VAC

NEUTRAL

120VAC

24 Volt

(Hot)
Heat

RH

Y2

W2

Jumper

Fault

Indicator

or

System

Malfunction

Switch

Comfort Alert II Module

or Similar System

Malfunction Module

O/B

Figure 5 – Single Stage or Multi-Stage System (No Heat Pump) with Two Transformers

Single

Stage 1

(SS1)

Multi-

Stage 2

(MS2)

No

Output

Cool

Mode

2nd

Stage

Cool Mode

1st Stage

Blower/

Circulator

Fan Energized

on Call for

Cool (and

Heat if

configured
for Electric

Heat)

No Output

Heat Mode

2nd Stage

Heat

Mode

1st Stage

Optional

24 Volt

(Com-

mon)

Fault

Indicator

(NOT

USED)

24 Volt

(Hot)

Cool

System

Y

G

W/E

C

L

RC

CLASS II

TRANSFORMER

HOT

24VAC

NEUTRAL

120VAC

24 Volt

(Hot)
Heat

RH

120VAC

Remove Jumper Wire
between RH & RC

HOT

24VAC

NEUTRAL

CLASS II

TRANSFORMER

HEATING

COOLING

Y2

W2

Jumper

O/B

O

Energized Constantly

in Cool Mode

B

Energized Constantly

in Heat, Off,

Emergency

Mode

Single Stage

3-wire

Zone Valve

application

Blower/Circulator

Fan Energized

Opens

Valve

(4)

Constant

24 Volt

(Com-

mon)

24 Volt

(Hot)

Cool

System

6

Y

W

C

RC

CLASS II

TRANSFORMER

HOT

24VAC

NEUTRAL

120VAC

24 Volt

(Hot)
Heat

(5)

RH

G

Jumper

Closes

Valve

(6)

Figure 6 – 3-Wire (SPDT) Heat Only Zone Valve Wiring