INSTALLER/CONFIGURATION MENU

With thermostat in Heat, Cool or Auto, in normal operation, press the Menu button for at least 5 seconds. The display will show
item #1 in the table below. Press Menu button to advance to the next menu item. Press

or

to change an item option.

Shaded items not available on 1F83 model.

INSTALLER/CONFIGURATION MENU

MENU

REF.

HP SS

PRESS

BUTTON

DISPLAYED

(FACTORY DEFAULT)

Press

or

to

select from listed options

COMMENTS

1

1

1

MENU

(MS 2)

HP 1, HP 2, SS 1

Selects Multi-Stage (MS 2 No Heat Pump),

Heat Pump 1 (HP 1, 1 compressor),

or Single Stage (SS 1), Heat Pump 2 (HP 2, 2

compressor or 2 speed compressor)

2

2

2

MENU

(GAS) for SS or MS

(ELE) for HP

ELE

GAS setting: furnace controls the blower

ELE setting: thermostat controls the blower

3

3

3

MENU

CS (0)

(Disabled)

1, 2, 3, 4, 5, 6

Selects Cool Savings

Value 1 (low) to 6 (high), Value 0 Disables Feature

4

4

4

MENU

E (On)

OFF

Selects Energy Management Recovery (EMR)

On or OFF. NA 1F83.

5

5

MENU

CR Heat (ME)

SL, FA

Adjustable Anticipation:

Selects heating cycle rate for MS or SS

6

5

MENU

CR Heat Pump

(ME)

SL, FA

Adjustable Anticipation (Heat Pump) (only

when heat pump selected in #1)

7

6

6

MENU

CR Cool (ME)

or

CR Emer (FA)

SL, FA

SL

Adjustable Anticipation: Selects the cycle rate for

cooling (only when MS 2 or SS 1 is selected in

item 1.) or Selects the cycle rate for Emergency

mode and Auxiliary stage if Heat Pump is

selected in item 1.

8

7

7

MENU

CL (OFF)

CL On

Compressor Lockout Time

9

8

8

MENU

Heat Auto

Cool Off

Heat Cool Off,

Heat Off with Fan icon,

Heat Off without Fan icon

Cool Off, Auto Off

System Mode Confi guration

with Automatic Changeover capability

10

9

9

MENU

dL (On)

dL OFF

Selects Display Light On or OFF

11

10

10

MENU

0

(current temperature)

1 HI, 2 HI, 3 HI, 4 HI,

1 LO, 2 LO, 3 LO, 4 LO

Adjustable Ambient Temperature Display

12

11

11

MENU

°

F

°

C

Selects Fahrenheit/Celsius Temperature Display

13

12

12

MENU

L Heat

(90)

L 62 to L 89

Selects Limited HEAT Range

14

13

13

MENU

L Cool

(45)

L 46 to L 82

Selects Limited COOL Range

15

14

14

MENU

P3

P0, P2

Defaults for 5-1-1 programming (P3) but non-

programmable (PO) or 5-2 programming (P2)

is available on most models. NA 1F83.

16

15

15

MENU

Heat AS (On)

OFF

Automatic Schedule for heat mode. NA 1F83.

NA to Cool only system.

17

16

16

MENU

Cool AS (On)

OFF

Automatic Schedule for cool mode. NA 1F83.

NA to Heat only system.

18

17

MENU

Heat FA (On)

OFF

Fast Heat option may be disabled by

selecting OFF. NA to SS confi g.

NA to Cool only system.

19

18

MENU

Cool FA (On)

OFF

Fast Cool option may be disabled by

selecting OFF. NA to SS confi g.

NA to Heat only system.

20

19

17

MENU

CA (OFF)

On

Selects active Comfort Alert On or OFF.

Requires CA II Module. (1F85CA only)

21

20

18

MENU

dS (On)

OFF

Selects Automatic daylight Savings Time option

On or OFF. NA 1F83.

22

21

19

MENU

Change Filter (OFF)

On

Selects Filter Change-out Indicator On or OFF.

MENU

Change Filter (200 h)

25-1975 h

Change Filter time in 25 hour increments. This
menu only appears if On is selected in above.

23

22

20

MENU

Cool On (o)

Heat On (b)

Selects operation of the reversing valve terminal

(O/B) output as an O or B terminal.

24

23

21

RUN

SCHED

Returns to Normal Operation