Figure 7 - unit dimensions, Table 6: unit clearances, Detail a – York DJ150 User Manual

Page 13: Detail b, Detail c

Advertising
background image

035-19046-002-B-0104

Unitary Products Group

13

NOTE:

A one-inch clearance must be provided between
any combustible material and the supply ductwork
for a distance of 3 feet from the unit.

NOTE:

If the unit includes gas heating, locate the unit so
the flue exhaust is at least:

•

Three (3) feet above any forced air inlet located within 10
horizontal feet (excluding those integral to the unit).

•

Four (4) feet below, four (4) horizontal feet from, or one
(1) foot above any door or gravity air inlet into the build-
ing.

•

Four (4) feet from electric meters, gas meters, regula-
tors, and relief equipment.

FIGURE 7 -

UNIT DIMENSIONS

50-3/4

4-1/4

59

30-3/16

24-3/16

17-3/16

27

89

11-1/2

LEFT

FRONT

For Drain Dimensions

See Detail C

See Detail A

119-7/16

Power

Entry

2-1/2

Con-

venience

Outlet

For

Baserail

Dimensions

See

Detail B

6-3/16

30-11/32

Control

Entry 7/8

Con-

venience

Outlet

Power

Entry

7/8

TABLE 6:

UNIT CLEARANCES

Top

*

*.

Units must be installed outdoors. Overhanging struc-
ture or shrubs should not obstruct condenser air dis-
charge outlet.

72”

Right

12”

Front

†

†.

The products of combustion must not be allowed to
accumulate within a confined space and re-circulate.

36”

Left

36”

Rear

‡

‡.

To remove the slide-out drain pan, a rear clearance of
sixty inches is required. If space is unavailable, the
drain pan can be removed through the front by separat-
ing the corner wall.

36”

Bottom

**

**.

Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.

0”

5 - 1 / 4

B a s e

P a n

1 7 - 1 3 / 1 6

V i e w o f W a l l A c r o s s f r o m C o i l

G a s P i p e I n l e t

DETAIL A

3 - 3 / 4

3 - 9 / 1 6

2 - 3 / 8

DETAIL B

5 - 3 / 8

DETAIL C

Advertising