CHARGING THE UNIT

The DJ150 (12-1/2 Ton) High Efficiency Unit, uses a TXV
metering device. Charge unit to 10º sub-cooling at the TXV.

TROUBLESHOOTING

PREDATOR

MAGNUM FLASH CODES

Various flash codes are utilized by the unit control board
(UCB) to aid troubleshooting. Flash codes are distinguished
by the short on and off cycle used (approximately 200ms on
and 200ms off). To show normal operation, the control board
flashes a 1 second on, 1 second off “heartbeat” during normal
operation. This is to verify that the UCB is functioning cor-
rectly. Do not confuse this with an error flash code. To prevent
confusion, a 1-flash, flash code is not used.

Current alarms are flashed on the UCB LED. The alarm his-
tory can be checked by pressing and releasing the ALARMS
button on the UCB. The UCB will cycle through the last five
(5) alarms, most recent to oldest, separating each alarm flash
code by approximately 2 seconds.

In some cases, it may be necessary to “zero” the ASCD for
the compressors in order to perform troubleshooting. To reset
all ASCDs for one cycle, press and release the UCB TEST
button once.

Troubleshooting of components may require open-
ing the electrical control box with the power con-
nected to the unit. Use extreme care when
working with live circuits!
Check the unit name-
plate for the correct line voltage and set the voltme-
ter to the correct range before making any
connections with line terminals.

When not necessary, shut off all electric power to the
unit prior to any of the following maintenance proce-
dures so as to prevent personal injury.

Label all wires prior to disconnection when servicing
controls. Wiring errors can cause improper and dan-
gerous operation which could cause injury to person
and/or damage unit components. Verify proper oper-
ation after servicing.

TABLE 28: UNIT CONTROL BOARD FLASH CODES

Flash Code

Description

On Steady

Control Failure - Replace Control

Heart Beat

Normal Operation

1 Flash

Not Applicable

2 Flashes

Control waiting ASCD

*

*.

These flash codes do not represent alarms.

3 Flashes

HPS1 - Compressor Lock out

4 Flashes

HPS2 - Compressor Lock out

5 Flashes

LPS1 - Compressor Lock out

6 Flashes

LPS2 - Compressor Lock out

7 Flashes

FS1 - Compressor Lock out

8 Flashes

FS2 - Compressor Lock out

9 Flashes

Ignition Control Locked Out/
Ignition Control Failure / Limit Switch Trip / No
Jumper Plug in Heat Section

10 Flashes

Compressors Locked Out On Low

Outdoor Air Temperature

*

11 Flashes

Compressors Locked Out Because The

Economizer Is Using Free Cooling

*

12 Flashes

Fan Overload Switch Trip - Not Applicable On This
Unit

13 Flashes

Compressor Held Off Due To Low Voltage*

14 Flashes

EEPROM Storage Failure (Control Failure)

OFF

No Power or Control Failure

TABLE 29: IGNITION CONTROL FLASH CODES

FLASHES

FAULT CONDITIONS

CHECK

STEADY ON

Control Failure

Control

HEARTBEAT

Normal Operation

1

Not Applicable

2

Pressure Switch
Stuck Closed

Pressure Switch

3

Pressure Switch Failed
To Close

Venter Pressure Switch
Vent Blocked

4

Limit Switch Open

Main Limit
AUX Limit

5

Flame Present With Gas
Off First Stage Gas Valve
Energized With W1 Off
Second Stage Gas Valve
Energized With First
Stage
Gas Valve Off

Gas Valve

6

Ignition Lockout

Gas Flow
Gas Pressure
Gas Valve
Flame Sensor

STEADY OFF

No Power Or Control
Failure

24VAC or Control