Installation – York DJ150 User Manual

Page 8

Advertising
background image

035-19046-002-B-0104

8

Unitary Products Group

INSTALLATION

INSTALLATION SAFETY INFORMATION

Read these instructions before continuing this appliance
installation. This is an outdoor combination heating and cool-
ing unit. The installer must assure that these instructions are
made available to the consumer and with instructions to
retain them for future reference.

1.

Refer to the furnace rating plate for the approved type of
gas for this furnace.

2.

Install this furnace only in a location and position as
specified on Page 11 of these instructions.

3.

Never test for gas leaks with an open flame. Use com-
mercially available soap solution made specifically for
the detection of leaks when checking all connections, as
specified on Pages 8, 24, 25 and 40 of these instruc-
tions.

4.

Always install furnace to operate within the furnace's
intended temperature-rise range with the duct system
and within the allowable external static pressure range,
as specified on the unit name/rating plate, specified on
Page 42 of these instructions.

5.

This equipment is not to be used for temporary heating
of buildings or structures under construction.

PRECEDING INSTALLATION

1.

Remove the two screws holding the brackets in the front,
rear and compressor side fork-lift slots.

TC

Technicoat Condenser Coil & Coil Guard

TD

Technicoat Condenser Coil & Dirty Filter Switch

TG

Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch

TJ

Technicoat Evaporator Coil

TL

Technicoat Evaporator Coil & Coil Guard

TM Technicoat Evaporator Coil & Dirty Filter Switch

TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch

TS

Technicoat Evaporator & Condenser Coils

TU

Technicoat Evaporator & Condenser Coils & Coil Guard

TV

Technicoat Evaporator & Condenser Coils & Dirty Filter Switch

TY

Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch

FIRE OR EXPLOSION HAZARD

Failure to follow the safety warning exactly could
result in serious injury, death or property damage.

Never test for gas leaks with an open flame. use a
commercially available soap solution made specifi-
cally for the detection of leaks to check all connec-
tions. A fire or explosion may result causing property
damage, personal injury or loss of life.

FIGURE 1 -

UNIT SHIPPING BRACKET

Bracket
Screws

Turn down

Advertising