TABLE 4: DH 180 COOLING CAPACITIES (15 TON) (CONTINUED)

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

115°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

KW

SENSIBLE CAPACITY, MBH

ENTERING DRY BULB, °F

CFM

WB

°F

90

85

80

75

70

65

4500

77

184.5

17.8

95.8

74.4

53.0

-

-

-

72

170.3

16.9

122.3

100.9

79.5

58.1

-

-

67

156.0

16.0

148.8

127.4

106.0

84.6

63.2

-

62

146.5

16.1

146.5

146.5

131.6

110.3

88.9

67.5

57

142.7

16.4

142.7

142.7

128.2

106.8

85.5

64.1

5250

77

189.3

17.9

117.2

82.8

57.5

-

-

-

72

174.6

17.0

136.8

111.5

86.3

61.0

-

-

67

160.0

16.1

156.4

140.3

115.0

89.7

64.5

-

62

150.2

16.2

150.2

150.2

142.8

117.6

92.3

67.0

57

146.3

16.5

146.3

146.3

139.1

113.8

88.6

63.3

6000

77

194.0

18.0

138.6

91.2

62.0

-

-

-

72

179.0

17.1

151.3

122.2

93.0

63.8

-

-

67

164.0

16.2

164.0

153.2

124.0

94.8

65.7

-

62

154.0

16.3

154.0

154.0

154.0

124.8

95.7

66.5

57

150.0

16.6

150.0

150.0

150.0

120.8

91.7

62.5

6750

72

182.8

17.2

166.5

133.3

100.1

66.9

-

-

67

167.5

16.3

167.5

162.1

133.5

100.3

67.1

-

62

157.3

16.4

157.3

157.3

157.3

124.1

90.9

57.7

57

153.2

16.7

153.2

153.2

153.2

120.0

86.8

53.6

7500

72

186.6

17.3

181.8

144.5

107.3

70.0

-

-

67

171.0

16.4

171.0

171.0

143.0

105.7

68.5

-

62

160.6

16.5

160.6

160.6

160.6

123.3

86.1

48.8

57

156.4

16.8

156.4

156.4

156.4

119.1

81.9

44.6

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Perfor-

mance Table for the KW of the supply air blower motor.

2. These ratings include the condenser fan motors (Total 2.3 KW) and the compressor motors but not the supply air blower motor.

Nominal Rating