TABLE 5: DH 210 COOLING CAPACITIES (17.5 TON) (CONTINUED)

AIR ON

EVAPORATOR

COIL

TEMPERATURE OF AIR ON CONDENSER COIL

115°F

125°F

TOTAL

CAP.

1

MBH

POWER

INPUT

2

KW

SENSIBLE CAPACITY, MBH

TOTAL

CAP.

1

MBH

POWER

INPUT

2

KW

SENSIBLE CAPACITY, MBH

ENTERING DRY BULB, °F

ENTERING DRY BULB, °F

CFM

WB

°F

90

85

80

75

70

65

90

85

80

75

70

65

5250

77

217.8

12.5

112.3

87.3

62.4

-

-

-

207.3

10.1

108.4

83.5

58.5

-

-

-

72

199.9

12.2

143.0

118.0

93.1

68.1

-

-

189.9

9.9

138.0

113.1

88.1

63.2

-

-

67

182.0

12.0

173.7

148.7

123.8

98.9

73.9

-

172.5

9.7

167.6

142.6

117.7

92.8

67.8

-

62

169.7

11.8

169.7

169.7

146.7

121.7

96.8

71.8

163.2

9.5

163.2

163.2

140.6

115.6

90.7

65.7

57

170.9

11.8

170.9

170.9

146.0

121.1

96.1

71.2

165.4

9.6

165.4

165.4

138.8

113.8

88.9

63.9

6125

77

223.9

16.9

142.1

98.9

69.4

-

-

-

212.0

16.5

141.0

95.0

65.5

-

-

-

72

205.5

16.5

162.5

133.0

103.5

74.1

-

-

194.2

16.2

157.5

128.0

98.5

69.1

-

-

67

187.1

16.1

182.9

167.2

137.7

108.2

78.7

-

176.5

15.8

174.0

161.1

131.6

102.1

72.6

-

62

174.4

15.8

174.4

174.4

163.1

133.6

104.2

74.7

167.0

15.6

167.0

167.0

157.2

127.7

98.2

68.7

57

175.7

15.8

175.7

175.7

162.4

132.9

103.4

74.0

169.2

15.7

169.2

169.2

155.2

125.7

96.2

66.7

7000

77

229.9

21.2

172.0

110.4

76.4

-

-

-

216.8

23.0

173.6

106.4

72.4

-

-

-

72

211.0

20.7

182.0

148.0

114.0

80.0

-

-

198.6

22.5

177.0

143.0

109.0

74.9

-

-

67

192.1

20.2

192.1

185.6

151.6

117.6

83.6

-

180.4

22.0

180.4

179.5

145.5

111.5

77.5

-

62

179.1

19.9

179.1

179.1

179.6

145.6

111.6

77.5

170.8

21.6

170.8

170.8

170.8

139.7

105.7

71.7

57

180.4

19.9

180.4

180.4

178.8

144.8

110.8

76.7

173.1

21.7

173.1

173.1

171.6

137.5

103.5

69.5

7875

72

215.7

20.8

200.1

161.4

122.6

83.9

-

-

203.1

22.6

195.0

156.3

117.5

78.8

-

-

67

196.4

20.3

196.4

193.2

163.1

124.4

85.6

-

184.5

22.1

184.5

184.1

156.9

118.2

79.4

-

62

183.1

20.0

183.1

183.1

183.4

144.6

105.9

67.1

174.7

21.7

174.7

174.7

174.7

137.4

98.7

59.9

57

184.4

20.0

184.4

184.4

183.6

144.9

106.1

67.4

177.0

21.8

177.0

177.0

176.3

137.5

98.8

60.0

8750

72

220.4

20.9

218.2

174.8

131.3

87.8

-

-

207.7

22.7

207.7

169.5

126.1

82.6

-

-

67

200.7

20.4

200.7

200.7

174.6

131.1

87.7

-

188.7

22.2

188.7

188.7

168.4

124.9

81.4

-

62

187.1

20.1

187.1

187.1

187.1

143.6

100.2

56.7

178.6

21.8

178.6

178.6

178.6

135.1

91.6

48.1

57

188.5

20.1

188.5

188.5

188.5

145.0

101.5

58.1

181.0

21.9

181.0

181.0

181.0

137.5

94.0

50.5

1. These capacities are gross ratings. For net capacity, deduct the air blower motor, MBH = 3.415 x KW. Refer to the appropriate Blower Performance

Table for the KW of the supply air blower motor.

2. These ratings include the condenser fan motors (Total 1 KW) and the compressor motors but not the supply air blower motor.