15 supply air blower performance (25 ton), Gas heat 300 mbh - bottom duct, Connections – York DH 300 User Manual

Page 26

Advertising
background image

262260-YTG-E-1008

26

Johnson Controls Unitary Products

NOTES:

1. Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil.
2. Refer to the additional Static Resistances table.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the
total static pressure of the blower.
* Do NOT close the pulley below 1 turn open.
** Factory setting.

TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT

300 MBH - BOTTOM DUCT CONNECTIONS

BLOWER

SPEED,

(RPM)

MOTOR

PULLEY

(TURNS

OPEN)*

CFM

7500

8750

10000

11250

12500

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

208 VOLT AND STANDARD DRIVE

975

6.0

1.2

5.9

4.9

5.0

7.3

6.0

-

-

-

-

-

-

-

-

-

1005

5.0

1.4

6.2

5.1

0.7

7.7

6.3

-

-

-

-

-

-

-

-

-

1040

4.0

1.6

6.6

5.4

0.9

8.1

6.7

0.2

9.7

8.0

-

-

-

-

-

-

1070

3.0

1.8

6.9

5.7

1.1

8.5

7.0

0.4

10.2

8.3

-

-

-

-

-

-

1100

2.0

2.0

7.3

6.0

1.3

8.9

7.3

0.6

10.6

8.7

-

-

-

-

-

-

1135

1.0

2.2

7.7

6.3

1.6

9.3

7.6

0.8

11.1

9.1

-

-

-

-

-

-

1165

0.0

2.4

8.0

6.6

1.8

9.7

8.0

1.0

11.6

9.5

0.2

13.5

11.0

-

-

-

208 VOLT AND HIGH STATIC DRIVE

1140

6.0

2.2

7.7

6.3

1.6

9.4

7.7

0.9

11.2

9.2

-

-

-

-

-

-

1180

5.0

2.5

8.2

6.7

1.9

9.9

8.1

1.2

11.8

9.7

0.3

13.7

11.2

-

-

-

1215

4.0

2.7

8.6

7.0

2.1

10.4

8.5

1.4

12.3

10.1

0.6

14.3

11.7

-

-

-

1255

3.0

3.0

9.1

7.4

2.4

11.0

9.0

1.7

12.9

10.6

0.9

15.0

12.3

-

-

-

1290

2.0

3.2

9.5

7.8

2.7

11.5

9.4

2.0

13.5

11.1

1.2

15.6

12.8

-

-

-

1330

1.0

3.5

10.0

8.2

3.0

12.0

9.9

2.3

14.1

11.6

1.5

16.4

13.4

-

-

-

1365

0.0

3.7

10.5

8.6

3.2

12.6

10.3

2.6

14.7

12.1

1.8

17.0

13.9

-

-

-

230/460/575 VOLT AND STANDARD DRIVE

975

6.0*

1.4

5.9

4.9

1.0

7.3

6.0

0.5

8.8

7.2

-

-

-

-

-

-

1005

5.0

1.6

6.2

5.1

1.2

7.7

6.3

0.7

9.2

7.6

0.1

10.9

8.9

-

-

-

1040

4.0

1.8

6.6

5.4

1.4

8.1

6.7

0.9

9.7

8.0

0.3

11.4

9.4

-

-

-

1070

3.0

2.0

6.9

5.7

1.6

8.5

7.0

1.1

10.2

8.3

0.6

11.9

9.8

-

-

-

1100

2.0

2.1

7.3

6.0

1.8

8.9

7.3

1.3

10.6

8.7

0.8

12.4

10.2

0.2

14.3

11.7

1135

1.0

2.4

7.7

6.3

2.0

9.3

7.6

1.6

11.1

9.1

1.0

13.0

10.6

0.4

14.9

12.2

1165

0.0

2.6

8.0

6.6

2.2

9.7

8.0

1.8

11.6

9.5

1.3

13.5

11.0

0.7

15.5

12.7

230/460/575 VOLT AND HIGH STATIC DRIVE

1140

6.0

2.4

7.7

6.3

2.1

9.4

7.7

1.6

11.2

9.2

1.1

13.1

10.7

0.5

15.0

12.3

1180

5.0

2.7

8.2

6.7

2.3

9.9

8.1

1.9

11.8

9.7

1.4

13.7

11.2

0.8

15.8

12.9

1215

4.0

2.9

8.6

7.0

2.6

10.4

8.5

2.2

12.3

10.1

1.7

14.3

11.7

1.1

16.4

13.5

1255

3.0

3.2

9.1

7.4

2.9

11.0

9.0

2.5

12.9

10.6

2.0

15.0

12.3

1.4

17.2

14.1

1290

2.0

3.4

9.5

7.8

3.1

11.5

9.4

2.7

13.5

11.1

2.2

15.6

12.8

-

-

-

1330

1.0

3.7

10.0

8.2

3.4

12.0

9.9

3.0

14.1

11.6

2.6

16.4

13.4

-

-

-

1365

0.0

3.9

10.5

8.6

3.7

12.6

10.3

3.3

14.7

12.1

2.9

17.0

13.9

-

-

-

15 HP Motor is required.