TABLE 16: BLOWER MOTOR AND DRIVE DATA

MODEL

SIZE

DRIVE

BLOWER

RANGE

(RPM)

MOTOR

1

ADJUSTABLE MOTOR PULLEY

FIXED BLOWER PULLEY

BELT

(NOTCHED)

HP FRAME

EFF.

(%)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

OUTSIDE

DIA.
(IN.)

PITCH

DIA.
(IN.)

BORE

(IN.)

DESIG-

NATION

PITCH

LENGTH

(IN.)

QTY.

15 TON

Standard 850/1065

5

184 T

83

1VP56

5.35

4.3-5.3

2

1-1/8

BK90

8.75

8.4

1

BX70

82.8

1

High

Static

965/1190

BK80

7.75

7.4

1

BX68

69.8

1

17.5 &

20 TON

Standard 870/1025

7.5

213 T

89

1VP68

6.75

5.5-6.5

2

1-3/8

BK120

11.75

11.4

1-3/16

BX83

84.8

1

High

Static

950/1120

BK110

10.75

10.4

1-3/16

BX81

82.8

1

25 TON

Standard 950/1120 10

215 T

89.5

1VP68

6.75

5.5-6.5

2

1-3/8

1B5V110

11.3

11.1

1-7/16

BX81

82.8

1

High

Static

1140/1365 15

254 T

91

1VP75X

7.5

6.2-7.4

1-5/8

1B5V94

9.7

9.5

1-7/16

5VX840

84.0

1

1. All motors have a nominal speed of 1800 RPM, a 1.15 service factor and a solid base. They can operate to the limit of their service factor because

they are located in the moving air, upstream of any heating device.

2. Do NOT close this pulley below 1 turn open.

TABLE 17: STATIC RESISTANCES

1

DESCRIPTION

RESISTANCE, IWG

CFM

15 TON

17.5 TON

20 TON

25 TON

4500

6000

7200

6000

8000

9000

6000

7000

9400

7500

10000

12500

WET COIL

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

ELECTRIC HEAT
OPTIONS
(DH models only)

18kW

0.3

0.4

0.4

0.4

0.4

0.5

0.4

0.4

0.5

0.4

0.6

0.6

36kW

0.3

0.4

0.5

0.4

0.5

0.5

0.4

0.5

0.5

0.5

0.5

0.6

54kW

0.4

0.5

0.5

0.5

0.5

0.6

0.5

0.5

0.6

0.5

0.6

0.7

72kW

0.4

0.5

0.5

0.5

0.5

0.6

0.5

0.5

0.6

0.5

0.6

0.7

ECONOMIZER OPTION

0.1

0.1

0.1

0.1

0.1

0.2

0.1

0.1

0.2

0.1

0.2

0.3

HORIZONTAL DUCT CONNECTIONS

2

0.1

0.2

0.3

0.2

0.3

0.5

0.2

0.3

0.5

0.3

0.5

0.6

1. Deduct theses resistance values from the available unit ESP values listed in the respective blower performance table except for

Horizontal Duct Connections.

2. Since the resistance to air flow will be less for horizontal duct connections than for bottom duct connections, add these pressures

to the ESP values on the respective unit’s blower performance table.

TABLE 18: POWER EXHAUST PERFORMANCE

MOTOR

SPEED

1

STATIC RESISTANCE OF RETRUN DUCTWORK, IWG

0.2

0.3

0.4

0.5

0.6

CFM

kW

CFM

kW

CFM

kW

CFM

kW

CFM

kW

HIGH

2

5250

0.83

4500

0.85

4200

0.88

3750

0.93

3000

0.99

MEDIUM

4900

0.77

3900

0.79

3500

0.82

2900

0.85

-

-

LOW

4400

0.72

3700

0.74

3000

0.78

-

-

-

-

1. Power exhaust motor is a 3/4 HP, PSC type with sleeve bearings, a 48 frame and inherent protection.
2. The factory setting.