Planning the Installation

975-0253-01-01

2–7

Guidelines for Matching PV Array Size to Xantrex Grid Tie Solar Inverter Input

For determining the number of panels required in the PV string (panels connected
in series), you must ensure that the following three requirements are met:

1. To avoid damage to the inverter, ensure that the PV array output will never

exceed 600 Vdc under any conditions.

2. Do not exceed the maximum array short circuit-current rating marked on the

inverter.

3. To achieve maximum energy harvest from your array, ensure that the V

MP

(voltage at maximum power) does not drop below 195 Vdc or increase above
550 Vdc under most conditions.

Guidelines to help you meet these requirements:

Consider the expected V

OC

of the string under all possible conditions. The

panel manufacturer provides a V

OC

rating per panel, but it is usually rated at

25 °C (77 °F). Ensure that the V

OC

rating at the coldest ambient temperature

does not exceed 600 V

OC

. Panel voltage increases in cold temperatures—the

panel manufacturer should be able to provide a coefficient of voltage increase
per degree.

Panel voltage decreases in high temperatures. This will affect the panels’
V

MP

. Again, the manufacturer’s coefficient must be used with the highest

expected temperature to determine the minimum V

MP

.

Once you know the specifications of your panels, all these factors will help
determine the maximum and minimum number of panels that can be used.

Visit the Support page at www.xantrex.com to use an online PV array sizing tool.

Grounding Requirements

AC Grounding

AC grounding is governed by local codes. Consult the local utility for specific
grounding requirements.

DC Grounding

The GT Inverter is designed to work with ungrounded PV arrays.

WARNING: Shock hazard

The GT Inverter must be grounded by connection to a grounded permanent wiring system.