Installing the Mounting Bracket

The mounting bracket for the GT Inverter allows the unit to be easily mounted and
removed for servicing. It has one hook that matches a corresponding hook on the
back side of the inverter.

Clearance Requirements

For optimal and safe operation, ensure there is adequate clearance around the
inverter. The minimum clearance recommendations in Table 2-2 assume a vertical
mounting. If clearances are less than these recommendations are used, additional
power reduction may occur at high ambient temperatures.

Figure 2-5 Mounting Bracket and GT Inverter

23.8 cm

9.4"

18.3 cm

7.2"

Mounting slots for securing the inverter

Mounting flanges

Rectangular slots × 8:
8 mm × 30 mm (5/16" × 1-3/16")

Table 2-2 Inverter Clearance Requirements

Location

Minimum Clearance

Above

30 cm (12 inches)

Below:

Inverter

Bracket

Outdoors:

100 cm (39 inches)

130 cm (51 inches)

Indoors: the same clearances are recommended but not required.

In front

Sufficient room to allow for easy access to read the display and to prevent
accidental contact with hot surface.

On sides

Units can be mounted side by side with no clearance between them, but
15 cm (6 inches) of clearance around the outermost two units is
recommended. In hot climates, some clearance between units may be
needed to prevent thermal derating.