Table 5: cooling capacities for dj210, Cooling capacities for dj210 – York DJ 180 User Manual

Page 11

Advertising
background image

261660-YTG-C-0707

Unitary Products Group

11

TABLE 5: COOLING CAPACITIES FOR DJ210

Air on Evaporator Coil

Temperature of Air on Condenser Coil

85°F

95°F

CFM

WB
(°F)

Total

Cap.

1

(MBH)

Total

2

Input

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

Total

Cap.

1

(MBH)

Total

2

Input

(kW)

Sensible Capacity (MBH)

*

Return Dry Bulb (°F)

86

83

80

77

74

71

68

86

83

80

77

74

71

68

6000

72

238.9 14.24 142.6 125.5 108.4 91.3 74.2

-

-

222.9 15.81 136.5 119.4 102.3 85.2 68.1

-

-

67

221.2 13.83 178.6 161.5 144.4 127.3 110.2 93.1 76.0 207.1 15.38 172.8 155.7 138.6 121.5 104.4 87.2 70.1

62

207.4 13.57 207.4 192.8 175.7 158.5 141.4 124.3 107.2 197.6 15.09 197.6 181.0 163.8 146.7 129.6 112.5 95.4

57

197.6 13.52 197.6 195.7 178.6 161.4 144.3 127.2 110.1 186.0 15.06 186.0 181.8 164.7 147.6 130.5 113.4 96.3

6500

72

246.1 14.36 154.5 135.8 117.0 98.3 79.5

-

-

231.8 15.91 149.7 130.9 112.2 93.4 74.6

-

-

67

227.9 13.95 193.5 174.7 156.0 137.2 118.4 99.7 80.9 215.4 15.48 189.4 170.7 151.9 133.2 114.4 95.6 76.9

62

213.7 13.69 213.7 206.4 189.7 170.9 152.2 133.4 114.6 205.5 15.19 205.5 197.1 179.6 160.9 142.1 123.4 104.6

57

203.6 13.64 203.6 202.6 192.8 174.1 155.3 136.5 117.8 193.5 15.15 193.5 191.3 180.6 161.8 143.1 124.3 105.5

7000

72

253.4 14.48 166.5 146.1 125.7 105.3 84.9

-

-

240.7 16.00 162.8 142.4 122.0 101.6 81.2

-

-

67

234.6 14.06 208.3 187.9 167.5 147.1 126.7 106.3 85.9 223.6 15.57 206.1 185.7 165.3 144.8 124.4 104.0 83.6

62

220.0 13.80 220.0 220.0 203.7 183.3 162.9 142.5 122.1 213.3 15.28 213.3 213.3 195.4 175.0 154.6 134.2 113.8

57

209.6 13.75 209.6 209.6 207.1 186.7 166.2 145.8 125.4 200.9 15.24 200.9 200.9 196.4 176.0 155.6 135.2 114.8

7875

72

258.4 14.56 180.9 157.6 134.4 111.2 87.9

-

-

243.3 16.09 176.8 153.6 130.3 107.1 83.8

-

-

67

239.3 14.14 225.6 202.4 179.1 155.9 132.6 109.4 86.1 226.0 15.65 217.3 199.8 176.5 153.3 130.0 106.8 83.5

62

224.4 13.88 224.4 224.4 216.2 193.0 169.7 146.5 123.2 215.6 15.36 215.6 215.6 206.7 183.4 160.2 136.9 113.7

57

213.8 13.82 213.8 213.8 212.5 189.2 166.0 142.8 119.5 203.0 15.32 203.0 203.0 200.8 177.6 154.3 131.1 107.8

8750

72

263.5 14.63 195.3 169.2 143.1 117.0 91.0

-

-

245.9 16.17 190.8 164.7 138.7 112.6 86.5

-

-

67

243.9 14.21 242.9 216.8 190.7 164.7 138.6 112.5 86.4 228.4 15.73 228.4 213.9 187.8 161.7 135.6 109.5 83.5

62

228.7 13.95 228.7 228.7 228.7 202.6 176.6 150.5 124.4 217.9 15.43 217.9 217.9 217.9 191.8 165.8 139.7 113.6

57

217.9 13.90 217.9 217.9 217.9 191.8 165.8 139.7 113.6 205.2 15.40 205.2 205.2 205.2 179.1 153.0 126.9 100.9

105°F

115°F

6000

72

210.2 17.65 131.0

113.9 96.8 79.7 62.6 -

-

197.6 19.49 125.5

108.3 91.2 74.1 57.0 -

-

67

195.1 17.21 167.5 150.4 133.3 116.2 99.1 82.0 64.9 183.1 19.04 162.2 145.1 128.0 110.9 93.8 76.7 59.6

62

186.9 17.01 186.9 170.6 153.5 136.4 119.3 102.2 85.1 176.3 18.92 176.3 160.2 143.1 126.0 108.9 91.8 74.7

57

174.4 16.80 174.4 172.3 155.2 138.1 121.0 103.9 86.8 162.8 18.55 162.8 162.8 145.7 128.6 111.5 94.4 77.3

6500

72

218.3 17.77 143.8 125.0 106.3 87.5 68.7

-

-

204.8 19.63 137.9 119.1 100.3 81.6 62.8

-

-

67

202.6 17.33 183.9 165.1 146.4 127.6 108.8 90.1 71.3 189.9 19.18 178.3 159.5 140.8 122.0 103.3 84.5 65.8

62

194.1 17.12 194.1 186.0 168.5 149.8 131.0 112.2 93.5 182.8 19.06 182.8 174.8 157.4 138.6 119.9 101.1 82.4

57

181.1 16.92 181.1 180.1 170.4 151.7 132.9 114.1 95.4 168.8 18.69 168.8 168.8 160.3 141.5 122.8 104.0 85.2

7000

72

226.4 17.89 156.6 136.2 115.7 95.3 74.9

-

-

212.1 19.77 150.3 129.9 109.5 89.0 68.6

-

-

67

210.1 17.45 200.2 179.8 159.4 139.0 118.6 98.2 77.8 196.6 19.32 194.4 174.0 153.6 133.2 112.7 92.3 71.9

62

201.3 17.24 201.3 201.3 183.6 163.1 142.7 122.3 101.9 189.3 19.20 189.3 189.3 171.7 151.3 130.9 110.5 90.0

57

187.8 17.03 187.8 187.8 185.6 165.2 144.8 124.4 104.0 174.8 18.82 174.8 174.8 174.8 154.4 134.0 113.6 93.2

7875

72

228.5 17.97 171.3 148.0 124.8 101.5 78.3

-

-

213.7 19.85 165.7 142.5 119.2 96.0 72.7

-

-

67

212.1 17.53 207.1 193.3 171.9 148.6 125.4 102.2 78.9 198.1 19.40 197.0 186.8 167.3 144.0 120.8 97.5 74.3

62

203.2 17.32 203.2 203.2 194.3 171.0 147.8 124.5 101.3 190.7 19.28 190.7 190.7 181.9 158.6 135.4 112.1 88.9

57

189.6 17.11 189.6 189.6 188.5 165.2 142.0 118.7 95.5 176.1 18.90 176.1 176.1 176.1 152.9 129.6 106.4 83.1

8750

72

230.6 18.05 186.0 159.9 133.8 107.7 81.7

-

-

215.2 19.94 181.1 155.1 129.0 102.9 76.8

-

-

67

214.0 17.61 214.0 206.7 184.4 158.3 132.2 106.1 80.0 199.5 19.48 199.5 199.5 181.0 154.9 128.8 102.7 76.6

62

205.0 17.40 205.0 205.0 205.0 178.9 152.8 126.8 100.7 192.1 19.36 192.1 192.1 192.1 166.0 139.9 113.8 87.8

57

191.3 17.19 191.3 191.3 191.3 165.2 139.1 113.0 87.0 177.4 18.98 177.4 177.4 177.4 151.3 125.2 99.1 73.1

125°F

6000

72 184.9

21.33

119.9

102.8

85.7

68.6

51.5

-

-

67

171.1 20.87 156.9 139.8 122.7 105.6 88.5 71.4 54.3

62

165.7 20.84 165.7 149.9 132.7 115.6 98.5 81.4 64.3

57

151.2 20.30 151.2 151.2 136.2 119.1 102.0 84.9 67.8

6500

72 191.4

21.49

132.0

113.2

94.4

75.7

56.9

-

-

67

177.1 21.03 172.7 154.0 135.2 116.5 97.7 79.0 60.2

62

171.5 21.00 171.5 163.6 146.3 127.5 108.8 90.0 71.3

57

156.5 20.46 156.5 156.5 150.1 131.4 112.6 93.8 75.1

7000

72

197.8 21.65 144.0 123.6 103.2 82.8 62.3

-

-

67

183.1 21.19 183.1 168.1 147.7 127.3 106.9 86.5 66.1

62

177.3 21.16 177.3 177.3 159.8 139.4 119.0 98.6 78.2

57

161.8 20.61 161.8 161.8 161.8 143.6 123.2 102.8 82.4

7875

72

198.9 21.74 160.2 136.9 113.7 90.4 67.2

-

-

67

184.1 21.27 184.1 180.2 162.6 139.4 116.2 92.9 69.7

62

178.2 21.24 178.2 178.2 169.5 146.3 123.0 99.8 76.5

57

162.6 20.69 162.6 162.6 162.6 140.5 117.3 94.0 70.8

8750

72

199.9 21.82 176.3 150.2 124.2 98.1 72.0

-

-

67

185.1 21.35 185.1 185.1 177.6 151.5 125.4 99.3 73.2

62

179.2 21.32 179.2 179.2 179.2 153.1 127.0 100.9 74.8

57

163.5 20.77 163.5 163.5 163.5 137.4 111.3 85.2 59.2

1.

The capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance table for the kW of the supply air blower motor.

2.

These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.