Table 1: sound power rating, Table 2: capacity ratings - (ari 360), Table 3: gas heat ratiings – York DJ 180 User Manual

Page 9: Sound power rating, Capacity ratings - (ari 360), Gas heat ratiings

Advertising
background image

261660-YTG-C-0707

Unitary Products Group

9

NOTE: All gas units are two-stage heating.
First stage is 50% of total.
S.S.E. = Steady State Efficiency (80%) - output divided by input.

TABLE 1: SOUND POWER RATING

1

UNIT

SIZE

CFM

ESP

BLOWER

SOUND POWER (db 10

-12

Watts)

Octave Band Centerline Frequency (Hz)

SWL

dB(A)

dB(A)

@

10Ft.

2

IWG

RPM

BHP

63

125

250

500

1,000

2,000

4,000

8,000

180

6,000

1.00

1,080

4.60

99

99

89

82

84

77

72

67

89

56

210/240

8,000

1.00

1,120

6.65

102

102

92

85

87

80

75

70

92

59

300

10,000

1.30

1160

12.5

108

108

98

91

93

86

81

76

98

65

1.

These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee
requiring a dBA value or sound data in any other form than sound power level ratings.

2.

At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)

1

1.

Certified in accordance with the Unitary Large Equip-
ment certification program which is based on ARI Stan-
dard 340/360.

MODEL

MBH

EER

2

2.

EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).

IPLV

3

3.

IPLV = Integrated Part Load Value.

COOLING ONLY

DJ180C/E00

178

12.0

12.5

DJ210C/E00

208

11.7

12.7

DJ240C/E00

230

11.3

12.0

DJ300C/E00

292

10.5

11.2

COOLING WITH GAS HEAT

DJ180N/S

178

12.0

12.5

DJ210N/S

208

11.7

12.7

DJ240N/S

230

11.3

12.0

DJ300N/S

292

10.5

11.2

COOLING WITH ELECTRIC HEAT

DJ180E18

178

12.0

12.5

DJ180E36

178

12.0

12.5

DJ180E54

176

11.8

12.2

DJ180E72

176

11.8

12.2

DJ210E18

208

11.7

12.7

DJ210E36

208

11.7

12.7

DJ210E54

206

11.5

12.4

DJ210E72

206

11.5

12.4

DJ240E18

230

11.3

12.0

DJ240E36

230

11.3

12.0

DJ240E54

228

11.1

11.7

DJ240E72

228

11.1

11.7

DJ300E18

292

10.5

11.2

DJ300E36

292

10.5

11.2

DJ300E54

290

10.3

11.0

DJ300E72

290

10.3

11.0

TABLE 3: GAS HEAT RATIINGS

MODEL

MBH INPUT

MBH OUTPUT

DJ180N/S24

300

240

DJ180N/S32

400

320

DJ210N/S24

300

240

DJ210N/S32

400

320

DJ240N/S24

300

240

DJ240N/S32

400

320

DJ300N/S24

300

240

DJ300N/S32

400

320

For units with VFD and electric or gas heat, the
speed of the indoor blower motor continues to
be controlled by duct static pressure via the
VAV control board.

If there are VAV boxes present in the duct sys-
tem, the boxes must be driven to the full-open
position using a customer-supplied power
source to assure adequate airflow across elec-
tric heating elements or gas heat exchanger
tubes.

Advertising