York DJ 180 User Manual

Page 27

Advertising
background image

261660-YTG-C-0707

Unitary Products Group

27

NOTE 1: HACR Type per NEC.

TABLE 20: DJ ELECTRICAL DATA WITH POWERED CONVENIENCE OUTLET (CONTINUED)

MODEL

(TON-

NAGE)

VOLTAGE

COMPRESSORS

OD FAN

MOTORS

FLA EACH

ID

BLOWER

MOTOR

FLA

CONV

OUTLET

AMPS

HEATER OPTION

MIN.

CIRCUIT

AMPACITY

(AMPS)

MAX.

FUSE/

BRKR

1

SIZE

(AMPS)

RLA

EACH

LRA

EACH

MODEL

KW

STAGES

AMPS

240

(20)

208

33.6

225

3.7

20.0

10.0

None

0.0

~

~

120.4

150

E18

13.5

1

37.5

120.4

150

E36

27.0

2

75.1

131.2

150

E54

40.6

2

112.6

178.4

200

E72

54.1

2

150.1

187.7

200

230

33.6

225

3.7

20.0

10.0

None

0.0

~

~

120.4

150

E18

18.0

1

43.3

120.4

150

E36

36.0

2

86.6

145.8

150

E54

54.0

2

129.9

167.4

175

E72

72.0

2

173.2

210.7

225

460

17.3

114

1.9

10.0

5.0

None

0.0

~

~

61.5

70

E18

18.0

1

21.7

61.5

70

E36

36.0

2

43.3

72.9

80

E54

54.0

2

65.0

83.7

90

E72

72.0

2

86.6

105.4

110

575

13.5

80

1.5

8.2

4.0

None

0.0

~

~

48.6

60

E18

18.0

1

17.3

48.6

60

E36

36.0

2

34.6

58.6

60

E54

54.0

2

52.0

67.2

70

E72

72.0

2

69.3

84.5

90

300

(25)

208

47.1

245

3.7

38.6

10.0

None

0.0

~

~

169.4

200

E18

13.5

1

37.5

169.4

200

E36

27.0

2

75.1

169.4

200

E54

40.6

2

112.6

201.6

225

E72

54.1

2

150.1

210.9

225

230

47.1

245

3.7

38.6

10.0

None

0.0

~

~

169.4

200

E18

18.0

1

43.3

169.4

200

E36

36.0

2

86.6

169.4

200

E54

54.0

2

129.9

190.7

225

E72

72.0

2

173.2

234.0

250

460

19.6

125

1.9

19.3

5.0

None

0.0

~

~

76.0

90

E18

18.0

1

21.7

76.0

90

E36

36.0

2

43.3

84.5

90

E54

54.0

2

65.0

95.3

110

E72

72.0

2

86.6

117.0

125

575

15.8

100

1.5

15.4

4.0

None

0.0

~

~

61.0

70

E18

18.0

1

17.3

61.0

70

E36

36.0

2

34.6

67.6

70

E54

54.0

2

52.0

76.2

90

E72

72.0

2

69.3

93.5

100

Advertising