Setting Parameters (continued)

CHARGED Indicator Setup (continued)

Trigger on Voltage and Time

When this mode is selected, the CHARGED indicator LED illuminates

when the voltage reaches the programmed level (Step A) and the amperage
remains positive for the specified time (Step B).

Step A Setting the Fully-Charged Voltage Level

1A. Press the SELECT button until the Voltage LED (

V

) is illuminated.

2A. Press the SELECT and RESET buttons simulataniously until the LED

display flashes.

3A. Press the RESET button to change the displayed voltage to the

desired fully charged voltage level.

• For a 12 VDC system, set this voltage between 14.3–14.9 volts for

lead-acid batteries.

• For a 24 VDC system, set this voltage between 28.6–29.6 volts for

lead-acid batteries.

• For a 48 VDC system, set this voltage between 57.2–59.2 volts for

lead-acid batteries.

Refer to the battery manufacturer’s recommendation for other types
of batteries.

4A. Press the SELECT button to accept the new value.

The selection range is between 10 to 64.9 VDC.

5A. Proceed to Step B.

14.4

Set Voltage Level

1A

4A

2A

Voltage LED Illuminates

to Indicate the Voltage

Function is Selected

3A

Figure 3-9

Setting the CHARGED Indicator Voltage Level