Reminders and Indicators (continued)

Low-Voltage Indicator

A voltage between 10 and 35 volts (10 and 64.9 volts for 48-volt systems)

can be specified to activate the low-voltage alarm. When the battery voltage
falls below this level, the voltage indicator (

V

) flashes approximately once

every four seconds.

To configure this alarm:

1. Press and hold the SELECT button until the dSF message is displayed,

then release.

2. Press and release the SELECT button until the bLO message is

displayed in the LED display.

3. Press and release the SELECT and RESET button together.

4. Press the RESET button until the desired voltage level is displayed.

5. Press the SELECT button to accept this value.

6. Press the SELECT button to return to the metering mode.

Figure 4-5

Low Voltage Indicator

dSF

4

1

5

2

3

Step 1 = dSF
Step 2 = bLO
Step 4 = value

6