Zhone Technologies IMACS Network Device User Manual

Page 23

Advertising
background image

Zhone Technologies, Inc.

IMACS Product Book, Version 4

March 2001

Page 19

Models 8903, 8905 and 8908 power supplies provide -48 VDC talk battery voltage from an AC input voltage. As
shown in table 4, the difference between models 8903 and 8905 is the input voltage range. Model 8905 has a much
wider input voltage range. Allowing it to operate from any AC line voltage, where as model 8903 has a limited
range. Model 8908 can only be used with the 900 chassis. It also has the benefit of a wide input voltage range but
with the addition of providing 300 watts of talk battery power.


Table 4—Power Supply Specifications

Model 8901 AC Power Supply 120/240 AC

Input Voltage

Self-detecting, 90VAC to 135 VAC at 60HZ
175 VAC to 264 VAC at 50 Hz

Input Frequency

47 to 63 Hz

Inrush Surge Current

Max. 12 amp peak at 264 VAC cold start

Output Power

55W Continuous

Maximum Number per system

2

Redundancy

Optional

Ventilation

Convection cooled

Protection

Unit is fused and protected from short circuits and over-
voltage

Approvals

UL 1459, EN 60950, CSA-C22.2 No.950, CE Mark

Model 8902 DC Power Supply 48 VDC

Input Voltage

-39 to -60 VDC

Inrush Surge Current

Maximum 12 amp at 60VDC

Output Power

55 Watts Continuous

Maximum Number per system

2

Redundancy

Optional

Ventilation

Convection cooled

Protection

Unit is fused protected from short circuits and overage

Unit is diode protected from reversed polarity

Approvals

UL 1459, EN60950, CSA-C22.2 No.950, CE Mark

Model 8907 DC Power Supply 24 VDC,

Input Voltage

18 to 36 VDC

Inrush Surge Current

Maximum 12 amp at 36 VDC

Output Power:

55 Watts Continuous

Maximum Number per system

2

Redundancy

Optional

Ventilation

Convection cooled

Protection

Unit is fuse protected from short circuits and over-voltage

Unit is diode protected from reverse polarity

Approvals

UL 1459, EN60950, CSA-C22.2 No.950, CE Mark

Model 8903 Power Supply 120 VAC

Input Voltage

90VAC to 132 VAC

Input Frequency

60 Hz

Inrush Surge Current

Max. 20amp peak at 132 VAC cold start

Output Voltage

-48.0 VDC

Maximum Number per system

2

Redundancy

Optional

Ventilation

Convection cooled

Protection

Unit is fused and protected from short circuits and over-
voltage

Approvals

UL 1459, UL 1950, CSA-C22.2 No.950


Advertising