INSTALLATION INSTRUCTIONS

16.5 HORIZONTAL SEPARATE FLUE INSTALLATION EXAMPLES - C82

IMPORTANT -

Make sure there is a minimum downward slope towards the outside of 1 cm per metre of duct length.

In the event of installation of the condensate collection kit, the angle of the drain duct must be directed towards the boiler.

N.B.:

For the C52 type, do not fit the flue and air duct terminals on opposite walls of the building.

The inlet flue must have a maximum length of 10 metres for C52 fumes outlets.

If the discharge duct is longer than 6 metres, install the condensate collection kit, supplied as an accessory, near the boiler

16.4 DIMENSIONS OF SEPARATE OUTLETS

CG_2124 / 0905_2305

L max = 10 m

(L1 + L2) max = 30 m

1010_0102/CG1643

CG_1643_FR / 1010_0101

IMPORTANT:

if fitting a single flue duct, make sure it is adequately insulated (e.g.: with glass wool) wherever the duct

passes through building walls. For detailed installation instructions, consult the technical data provided with the accessories.