Annual servicing, Draining the boiler circuit, Warnings – DE DIETRICH MS 24 User Manual

Page 89

Advertising
background image

89

71.03982.03 - EN

INSTALLATION INSTRUCTIONS

To optimise boiler efficiency, carry out the following annual controls:

• check the appearance and air-tightness of the gaskets of the gas and combustion circuits;

• check the state and correct position of the ignition and flame-sensing electrodes;

• check the state of the burner and make sure it is firmly fixed;

• check for any impurities inside the combustion chamber.

Use a vacuum cleaner to do this;

• check the gas valve is correctly calibrated;

• check the pressure of the heating system;

• check the pressure of the expansion vessel;

• check the fan works correctly;

• make sure the flue and air ducts are unobstructed.

WARNINGS

Before commencing any maintenance operations, make sure the boiler is disconnected from the power supply.

Afterwards, move the knobs and/or operating parameters of the boiler to their original positions.

28. ANNUAL SERVICING

Drain the boiler by opening the drain tap.
In boilers MS 24 MI and MS 24 MI FF the drain tap is located at the bottom while for boilers MS 24 and MS 24 FF it is
next to the pump (1 – fig. 15).

To drain the boiler using the drain tap located at the bottom, proceed as follows (fig. 15):

- close the boiler on/off valves;
- open the drain tap using an 8 mm hex wrench;
- drain the boiler;
- close the drain tap using the 8 mm hex wrench.

29. DRAINING THE BOILER CIRCUIT

CG_2284 / 1009_2405

Figure 15