InStallatIOn

commissioning

11. commissioning

11.1 commissioning

f

f Open a draw-off point until the appliance has filled up and

the pipework is free of air.

f

f Adjust the flow rate. For this, observe the maximum permis-

sible flow rate with a fully opened tap (see chapter "Specifi-

cation / Data table"). If necessary reduce the flow rate at the

butterfly valve of the safety assembly.

f

f Carry out a tightness check.

f

f Turn the temperature selector to maximum temperature.

f

f Switch the mains power ON.

f

f Check the function of the appliance.

f

f Check the function of the safety assembly.

11.1.1 appliance handover

f

f Explain the appliance function to users and familiarise them

with its operation.

f

f Make the user aware of potential dangers, especially the risk

of scalding.

f

f Hand over these instructions.

11.2 recommissioning

See chapter "Commissioning".

12. settings

12.2.1 limiting the temperature selection
You can adjust the temperature selection limitation beneath the

temperature selector.
Factory setting: Limited to 60 °C

f

f Set the temperature selector to "cold" and isolate the appli-

ance from the power supply.

f

f Remove the temperature selector and the control panel

cover.

1

2

26

�0

2�

79

�0

07

0

1 Limiter disc

2 Without limiter disc, maximum 82 °C

f

f You can set the limit to 45 °C / 60 °C by rotating the limiter

disc. After removing the limiter disc, the maximum tempera-

ture can be set.

f

f Replace the control panel cover and temperature selector.

13. shutting down

f

f Disconnect the appliance from the mains at the MCB/fuse in

the fuse box.

f

f Drain the appliance. See chapter "Maintenance / Draining the

appliance".