Specifications (cont.) – Veris Industries E50H5A Install User Manual

Page 2

Advertising
background image

ZL0117-0D

Page 2 of 28

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 08131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

Installation Guide

Power Monitoring

E50H2A, E50H5A

TM

CONTROL POWER

AC 5 VA max.; 90V min.

UL Maximums: 600V

L-L

(347V

L-N

); CE Maximum: 300V

L-N

DC* 3 W max.; UL and CE: 125 to 300VDC

Ride Through Time 100 msec at 120VAC

INPUT

Pulse Solid-state or mechanical contacts (current less than 1 mA);

E50H2: 1 pulse input; E50H5: 2 pulse inputs)

Minimum Pulse Width 20 msec

OUTPUT

Alarm Contacts (E50H2 only) N.C., static output; (30VAC/DC, 100mA max.@25°C, derate 0.56mA

per °C above 25°C)

RS-485 Port 2-wire, 9600 to 115.2 kbaud, BACnet MS/TP

MECHANICAL CHARACTERISTICS

Weight 0.62 lb (0.28 kg)

IP Degree of Protection

(IEC 60529)

IP40 front display; IP20 Meter

Display Characteristics Back-lit blue LCD

Terminal Block Screw Torque 0.37 to 0.44 ft-lb (0.5 to 0.6 N·m)

Terminal Block Wire Size 26 to 14 AWG (0.13 to 2.08 mm

2

)

Rail T35 (35mm) DIN Rail per EN50022

OPERATING CONDITIONS

Operating Temperature Range -30° to 70°C (22° to 158°F)

Storage Temperature Range -40° to 85°C (-40° to 185°F)

Humidity Range <95% RH noncondensing

Altitude of Operation 3000 m

COMPLIANCE INFORMATION

US and Canada CAT III, Pollution degree 2;

for distribution systems up to 347V

L-N

/600VAC

L-L

CE CAT III, Pollution degree 2;

for distribution systems up to 300V

L-N

Dielectric Withstand Per UL 508, EN61010

Conducted and Radiated

Emissions

FCC part 15 Class B, EN55011/EN61000 Class B (residential and light

industrial)

Conducted and Radiated

Immunity

EN61000 Class A (heavy industrial)

US and Canada (cULus) UL508 (open type device)/CSA 22.2 No. 14-05

Europe (CE) EN61010-1

* External DC current limiting is required, see fuse recommendations.