Bacnet programming information (cont.), Legend, Device object – Veris Industries E50H5A Install User Manual
Page 20

ZL0117-0D
Page 20 of 28
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 08131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Power Monitoring
E50H2A, E50H5A
TM
BACnet
Programming
Information
(cont.)
Legend
R/W
R=read only; R/W=read or write
NV
Value is stored in non-volatile memory. The value are still available if the meter experiences a power loss and reset.
Units
Lists the physical units that a register holds.
Device Object
Property
R/W
NV
Value Returned
Additional information
Object_Identifier
R/W
NV
Device<n>
n is the 7 digit ID # set in the ID1 & ID2 setup screens on the meter. The BACnet Device
ID is a decimal number from 1 to 4,193,999 that can be entered or viewed on the user
screens or through this property. The default value set at the factory is a psuedo-
random number from 1,000,000 to 3,097,151 to reduce the likelihood of conflicts if
multiple units are installed using their default IDs.
Object_Type
R
NV
Device (8)
Object_Name
R
NV
Veris E50 Series Energy Meter - S/N: <serial
number>
Vendor_Name
R
NV
Veris Industries, LLC
Vendor_Identifier
R
NV
133
Model_Name
R
NV
E50HxA Energy Meter
Firmware_Revision
R
NV
<Current Revision #>
“xyyy”.
This is the BACnet processor firmware version in the format <xyyy>, with an implied
decimal point between the first two digits (x.yyy)
Application_Software_ Version
R
NV
<Current version #>
“RS= xyyy, OS=xyyy, BACnet Gateway=xyyy”
The format <xyyy> has an implied decimal point between the first two digits (x.yyy)
Location
R/W
NV
<Location>
Limted to 64 Characters - Default value is “Installed location not yet identified”
Description
R
NV
Veris E50HxA DIN-Rail Energy Meter S/N:
<serial number>
Protocol_Version
R
NV
1
BACnet Protocol Version 1
Protocol_Revsion
R
NV
4
BACnet Protocol Revision 4
Local_Date
R
Date
Set via BACnet Time Synchronization only - reverts to Jan 1, 2000 if control power drops
Local_Time
R
Time
Set via BACnet Time Synchronization only - reverts to 12:00:00 AM if control power
drops
Segmentation_Supported
R
NV
NO_SEGMENTATION (3)
Segmentation is not supported
Max_Master
R/W
NV
1-127 (Factory Default is 127)
Highest possible MAC Address for Master nodes on the local MS/TP network
Max_Info_Frames
R
NV
1
Maximum number of information frames allowed before passing the MS/TP token
Max_APDU_Length_Accepted
R
NV
480
APDU_Timeout
R
NV
60000
Number_of_APDU_Retries
R
NV
0
System_Status
R
NV
Operational (0)
Protocol_Sevices_Supported
R
NV
0b0000000000001011010000000000000
011110000
Protocol_Object_Types_Supported
R
NV
0b1011000010000000000010000000000