INSTALLATION GUIDE
ADDRESS SELECTION SWITCHES
Each device on the N2 BUS must have a unique address. These switches must be set to assign a unique address before the device is connected to the N2 BUS. If an address is
selected which conflicts with another device on the N2 BUS, both devices will be unable to communicate.
When setting the N2 BUS address, choose an address number which is not in use. Only N2 addresses in the range of 1 to 63 may be used. Set the switches for the selected
address by following the diagram below. This address will be required when adding the meter to Metasys®.