INSTALLATION GUIDE

POINT MAP FOR H8026 (ENHANCED DATA STREAM), N2 PROTOCOL

NPT

NPA

UNITS

POINT DESCRIPTION

RANGE/VALUE

NOTES

BI

1

kWh, kW*

Consumption (accumulation)

100A: 0.0025 kWh/count
300A: 0.01 kWh/count
400A: 0.01 kWh/count
800A: 0.02 kWh/count
1600A: 0.04 kWh/count
2400A: 0.08 kWh/count

Intended for use as an accumulator (ACM) type. It should not be read as a binary status.

AI

1

kWh

Consumption

100A: 0 to 10737418.24
2400A: 0 to 343597383.7

Allows direct view of kWh accumulator as an AI point. For large values, BI-1 is more precise.

AI

2

kW

Real Power

100A: 0 to 83.1
2400A: 0 to 1995.3

AI

3

kVAR

Reactive Power

100A: 0 to 83.1
2400A: 0 to 1995.3

AI

4

kVA

VA (apparent power)

100A: 0 to 83.1
2400A: 0 to 1995.3

AI

5

Power Factor, total

0 to 1.0

Reads the effective power factor for all phases (not an average of AI-15, AI-16, and AI-17).

AI

6

kW

Average Real Power

100A: 0 to 83.1
2400A: 0 to 1995.3

Reads the average real power (kW). This is intended for demand window applications, where

this point is read at the end of each window and then reset via BO-2.

AI

7

kW

Mimimum Real Power

100A: 0 to 83.1
2400A: 0 to 1995.3

Reads the min. real power since it was reset via BO-2. Real power is internally monitored in

200msec intervals.

AI

8

kW

Maximum Real Power

100A: 0 to 83.1
2400A: 0 to 1995.3

Reads the max. (peak) real power since it was reset via BO-2. Peak power is internally

monitored in 200msec intervals.

AI

9

Volts

Voltage, Line-to-Line

0 to 480

Reads the average line to line voltages.

AI

10

Volts

Voltage, Line-to-Neutral

0 to 277

Reads the average line to neutral voltages.

AI

11

Amps

Current

100A: 0 to 100
2400A: 0 to 2400

Reads the current.

AI

12

kW

Real Power, ØA

100A: 0 to 27.7
2400A: 664.8

AI

13

kW

Real Power, ØB

100A: 0 to 27.7
2400A: 664.8

AI

14

kW

Real Power, ØB

100A: 0 to 27.7
2400A: 664.8

AI

15

Power Factor, ØA

0 to 1.0

AI

16

Power Factor, ØB

0 to 1.0

AI

17

Power Factor, ØC

0 to 1.0

AI

18

Volts

Voltage, ØA to ØB

190 to 480

The meter is powered by A-B voltage; it will not operate at low voltage.

AI

19

Volts

Voltage, ØB to ØC

0 to 480

AI

20

Volts

Voltage, ØA to ØC

0 to 480

AI

21

Volts

Voltage, ØA to Neutral

0 to 277

AI

22

Volts

Voltage, ØB to Neutral

0 to 277

AI

23

Volts

Voltage, ØC to Neutral

0 to 277

AI

24

Amps

Current, ØA

100A: 0 to 100
2400A: 0 to 2400

AI

25

Amps

Current, ØB

100A: 0 to 100
2400A: 0 to 2400

AI

26

Amps

Current, ØC

100A: 0 to 100
2400A: 0 to 2400

ADI

1

Amps

Preset kWh, LSW

-32768 to 32767

Allows the lower 16 bits of the kWh accumulator to be preset

ADI

2

Preset kWh, MSW

-32768 to 32767

Allows the upper 16 bits of the kWh accumulator to be preset

BO

1

Reset kWh

0 = NA
1 = Reset kWh

Resets the kWh accumulator to zero. The value will return to "off." **

BO

2

Reset Min/Max/Avg

0 = NA
1 = Reset min/max/avg

Command to "on" to reset the AI-5, AI-6, and AI-7. THe value will return to "off." **