Veris Industries H922 Install User Manual

Split-core current transducer, 0-5vdc output, Installation guide, Wiring example

Advertising
background image

6%2)3

CURRENT MONITORING

INSTALLATION GUIDE

Z201167-0E

PAGE 1

©2009 Veris Industries USA 800.354.8556 or 503.598.4564 / [email protected]

05092

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Split-Core Current Transducer,

0-5VDC Output

Installer’s Specifications

Sensor Power

Induced from monitored conductor

Insulation Class

600VAC RMS (UL), 300VAC RMS (CE)

Frequency

50/60Hz

Temperature Range

-15° to 60°C (5° to 140°F)

Humidity Range

10-90% RH non-condensing

Amperage Range

0-30/60/120 Amps (slide-switch selectable)

Output

0-5VDC

Hysteresis

10% of setpoint, typical

Safety

UL 508, IEC 61010-1: 2001 CAT III

Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2001,

Installation Category III or equivalent.

The product design provides for basic insulation only.

)";"3%0'&-&$53*$4)0$, &91-04*0/ 03"3$'-"4)

t 'PMMPXTBGFFMFDUSJDBMXPSLQSBDUJDFT

4FF/'1"&JOUIF64" PSBQQMJDBCMFMPDBMDPEFT

t 5IJTFRVJQNFOUNVTUPOMZCFJOTUBMMFEBOETFSWJDFECZRVBMJmFEFMFDUSJDBMQFSTPOOFM
t 3FBE VOEFSTUBOEBOEGPMMPXUIFJOTUSVDUJPOTCFGPSFJOTUBMMJOHUIJTQSPEVDU
t 5VSOPõBMMQPXFSTVQQMZJOHFRVJQNFOUCFGPSFXPSLJOHPOPSJOTJEFUIFFRVJQNFOU
t 6TFBQSPQFSMZSBUFEWPMUBHFTFOTJOHEFWJDFUPDPOmSNQPXFSJTPõ
 %0/05%&1&/%0/5)*4130%6$5'0370-5"(&*/%*$"5*0/
t 0OMZJOTUBMMUIJTQSPEVDUPOJOTVMBUFEDPOEVDUPST

'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTXJMMSFTVMUJOEFBUIPSTFSJPVTJOKVSZ

%"/(&3

Wiring ExamplE

H922

922

DimEnsions

/05*$&

t 5IJTQSPEVDUJTOPUJOUFOEFEGPSMJGFPSTBGFUZBQQMJDBUJPOT

t %POPUJOTUBMMUIJTQSPEVDUJOIB[BSEPVTPSDMBTTJmFEMPDBUJPOT

t 5IFJOTUBMMFSJTSFTQPOTJCMFGPSDPOGPSNBODFUPBMMBQQMJDBCMFDPEFT

t .PVOUUIJTQSPEVDUJOTJEFBTVJUBCMFmSFBOEFMFDUSJDBMFODMPTVSF

Removable Mounting Bracket

Self-gripping

Iris

1.0”

(25 mm)

0.8”

(21 mm)

1.1”

(26 mm)

3.1”

(79 mm)

2.8”

(70 mm)

Ø = 0.3”

(8 mm)

1.4”

(36 mm)

2.5”

(64 mm)

3.0”

(76 mm)

Bracket can be mounted
on either side for added
installation flexibility.

Use DIN Rail

Mounting clip

(Veris part

number AH01) to

mount on stan‑

dard DIN rail.

Fan or Pump

CONTROLLER

0-5 VDC

Analog

Input

MOTOR

CONTACTOR

Quick install

Disconnect and lock out power to the conductor to be monitored.

1.

Plan the installation:

2.

Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the iris, or “window” when it is installed
and keep the product at least 1/2” (13mm) from any uninsulated conductors (CE).
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.

Install mounting bracket

3.

Drill holes to mount the bracket to the chosen surface using the included screws.

Set the desired amperage range (30, 60, or 120 Amps).

4.

Wire the output connections between the sensor and the controller (0-5 VDC).

5.

Snap the sensor over the wire to be monitored and clip the assembly to the

6.

mounting bracket.

Scale the controller software to match the selected output.

7.