opEration

The H922 is a current transducer that senses current (amperage) in any of three
field-selectable ranges; zero-to-thirty, zero-to-sixty, or zero-to-one hundred twenty
amperes. These ranges represent the maximum current that can be applied to the
monitored conductor. The H922 transforms the monitored current into a 0-5VDC
output suitable for connection to building controllers or other appropriate data
acquisition equipment. The H922 requires no external power supply to generate its
output.

The H922 housing offers unprecedented mounting flexibility. The mounting bracket
can be attached in three different places. Additionally, the bracket is compatible with
the Veris AH01 DIN Rail clip, allowing DIN mounting.

notEs

For load currents less than sensor minimum rating:

Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.

3x

1A

DANGER: 5A CTs can present hazardous voltages.

Install CTs in accordance with manufacturer's instructions.

Terminate the CT secondary before applying current.

H68xx‑5A CT

240A

300A:

5A

4A

> 120A (Sensor max.)

For load currents greater than sensor maximum rating:

Use a 5 Amp (H68xx series) Current Transformer (CT) as shown.

CAUTION

RISK OF EQUIPMENT DAMAGE

t %FSBUFUIFQSPEVDUTNBYJNVNDVSSFOUGPSUIFOVNCFSPGUVSOT

UISPVHIUIFTFOTJOHXJOEPXVTJOHUIFGPMMPXJOHGPSNVMB

3BUFE.BY"NQTŸ/VNCFSPG5VSOT.BYNPOJUPSFE"NQT
FH"Ÿ5VSOT"NQTNBYJONPOJUPSFEDPOEVDUPS

t 'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTDBOSFTVMUJOPWFSIFBUJOH

BOEQFSNBOFOUFRVJQNFOUEBNBHF

Controller must be
programmed to account for the
extra turns. e.g., if three turns
pass through the sensor (as
shown) the normal controller
reading must be divided by 3.

< 3 A (Sensor Min.)

troublEshooting

Problem

Solution

No Reading at Controller

• Check polarity of sensor output connections.
• Check for output voltage at sensor.
• Check for amperage in the monitored conductor.
• Assure that sensor core mating surfaces are clean and

that the core clamp is completely closed.

scaling

Set range switch.

1.

120

60

30

Amperage Range
Selector Switch

120

60

30

Scale controller

2.

software to match
selected output.

SENSED AMPS

Selected Range*

0 VDC

0A

5 VDC

SENSOR OUTPUT

*Factory calibrated ranges selected