Installation guide – Veris Industries E8950 Install User Manual
Page 10

TM
E8950
INSTALLATION GUIDE
ZL0105-0B
PAGE 10
©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
02131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Enercept H8035 Series Energy Meters (all models)
The H8035 Series has 3 data objects and operates at 9600 baud.
Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Analog_input objects: (Read-only)
kWh Energy: Total
Accumulated Real Energy
AI1
kWH
0
40259/40260
kW: Total
Total Instantaneous Real Power
AI2
kW
1
40261/40262
Analog_Value objects: (can be written as well as read)
kWh Energy Reset
Write zero to reset
AV1
n/a
32767
40001
APPENDIX 1: DATA OBJECTS FOR SUPPORTED METERING DEVICES