Data Variable
Description
BACnet
Object
Units
COV_
Increment
Modbus
Address
Comments
Baud rate as conf by DIP
switches
integer (2400; 4800; 9600;
19200)
AI55
n/a
0
69
Analog_Value objects: (can be written as well as read)
Reset Min/Max/Avg Real Power
Write Zero to Reset Min/Max/
Avg kW
AV1
n/a
0
28
Returns random values if read.
Reset Energy Consumption
Write Zero to Reset kWh
Accumulator
AV2
n/a
0
1
Returns random values if read.
CT Scale
Amp rating of CT used (integer)
AV3
Amps
0
30
Sets the size of the external 5-Amp CTs used. Range is 1 to
5999. E.g. for 10A:5A CTs, set register to 10; for 4000A:5A
CTs, set register to 4000.
Over Voltage (AV6) Alarm
Threshold
Alarm if L-L Voltage>threshold
> 10 sec
AV4
Volts
0
31
Occurs if the average L-L voltage (AI6) is greater than
this threshold for at least 10 seconds. Units are absolute
voltage (using integer multiplier). Range = 0 to 65535;
Default = 65535
Under Voltage (AV6) Alarm
Threshold
Alarm if L-L Voltage<threshold
(ever)
AV5
Volts
0
32
Occurs if the average L-L voltage (AI6) is less than this
threshold at any time. Units are absolute voltage (using
integer multiplier). Range = 0 to 65535; Default = 0
Over Current (AV8) Alarm
Threshold
Alarm if Avg Current>threshold
(ever)
AV6
Amps
0
33
Occurs if the average current (AI8) is greater than this
threshold at any time. Units are absolute current
(usinginteger multiplier). Range = 0 to 65535; Default
= 65535
Under Current (AV8) Alarm
Threshold
Alarm if Avg Current<threshold
(ever)
AV7
Amps
0
34
Occurs if the average current (AI8) is less than this
threshold at any time. Units are absolute current
(usinginteger multiplier). Range = 0 to 65535; Default
= 0
Over kVA (AV5) Alarm Threshold
Alarm if kVA>threshold (ever)
AV8
kVA
0
35
Occurs if the total apparent power (AI5) is greater than
this threshold at any time. Units are absolute kVA (using
integer multiplier). Range = 0 to 65535; Default = 65535
Under kVA (AV5) Alarm
Threshold
Alarm if kVA<threshold (ever)
AV9
kVA
0
36
Occurs if the total apparent power (AI5) is less than this
threshold at any time. Units are absolute kVA (using
integer multiplier). Range = 0 to 65535; Default = 0
Meter Alarm Status (Latching)
bitmap of 8 alarms - bits 9-15
are all 0
AV10
n/a
0
37
Holds the state of the meter alarm latches. These alarms
are latching and must be cleared by the user. To reset any
alarm, read the register and then write the register with
the desired alarm bit cleared. Writing a 1 to any bit has
no effect.
bit 0 = over current
bit 1 = under current
bit 2 = over kVA
bit 3 = under kVA
bit 4 = over voltage
bit 5 = under voltage
bit 6 = phase loss A
bit 7 = phase loss B
bit 8 = phase loss C
bits 9-15 = 0
Phase Loss Threshold
Integer % of other phases
AV11
Percent
0
38
Phase Loss Threshold (0 to 100%, default = 65535): these
exist independently for all 3 phases (A, B, C). This register
sets the alarm threshold for all three phases. This setting
is the percent deviation of a phase from the average of
all 3 phases (register 8). The decision logic is constructed
so that normal power-ups do not trigger alarms. A phase
loss alarm will occur only if the following conditions are
met:
1. The average L-L voltage (register 8) is greater than 25V.
2. The L-N voltage on a phase (register 20, 21, or 22) is less
than the percent deviation set by this threshold.
3. This threshold is set between 0 and 100%.