Installation guide, E8950 – Veris Industries E8950 Install User Manual

Page 26

Advertising
background image

TM

E8950

INSTALLATION GUIDE

ZL0105-0B

PAGE 26

©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]

02131

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

Data Variable

Description

BACnet

Object

Units

COV_

Increment

Modbus

Address

Comments

Baud rate as conf by DIP

switches

integer (2400; 4800; 9600;

19200)

AI55

n/a

0

69

Analog_Value objects: (can be written as well as read)
Reset Min/Max/Avg Real Power

Write Zero to Reset Min/Max/

Avg kW

AV1

n/a

0

28

Returns random values if read.

Reset Energy Consumption

Write Zero to Reset kWh

Accumulator

AV2

n/a

0

1

Returns random values if read.

CT Scale

Amp rating of CT used (integer)

AV3

Amps

0

30

Sets the size of the external 5-Amp CTs used. Range is 1 to

5999. E.g. for 10A:5A CTs, set register to 10; for 4000A:5A

CTs, set register to 4000.

Over Voltage (AV6) Alarm

Threshold

Alarm if L-L Voltage>threshold

> 10 sec

AV4

Volts

0

31

Occurs if the average L-L voltage (AI6) is greater than

this threshold for at least 10 seconds. Units are absolute

voltage (using integer multiplier). Range = 0 to 65535;

Default = 65535

Under Voltage (AV6) Alarm

Threshold

Alarm if L-L Voltage<threshold

(ever)

AV5

Volts

0

32

Occurs if the average L-L voltage (AI6) is less than this

threshold at any time. Units are absolute voltage (using

integer multiplier). Range = 0 to 65535; Default = 0

Over Current (AV8) Alarm

Threshold

Alarm if Avg Current>threshold

(ever)

AV6

Amps

0

33

Occurs if the average current (AI8) is greater than this

threshold at any time. Units are absolute current

(usinginteger multiplier). Range = 0 to 65535; Default

= 65535

Under Current (AV8) Alarm

Threshold

Alarm if Avg Current<threshold

(ever)

AV7

Amps

0

34

Occurs if the average current (AI8) is less than this

threshold at any time. Units are absolute current

(usinginteger multiplier). Range = 0 to 65535; Default

= 0

Over kVA (AV5) Alarm Threshold

Alarm if kVA>threshold (ever)

AV8

kVA

0

35

Occurs if the total apparent power (AI5) is greater than

this threshold at any time. Units are absolute kVA (using

integer multiplier). Range = 0 to 65535; Default = 65535

Under kVA (AV5) Alarm

Threshold

Alarm if kVA<threshold (ever)

AV9

kVA

0

36

Occurs if the total apparent power (AI5) is less than this

threshold at any time. Units are absolute kVA (using

integer multiplier). Range = 0 to 65535; Default = 0

Meter Alarm Status (Latching)

bitmap of 8 alarms - bits 9-15

are all 0

AV10

n/a

0

37

Holds the state of the meter alarm latches. These alarms

are latching and must be cleared by the user. To reset any

alarm, read the register and then write the register with

the desired alarm bit cleared. Writing a 1 to any bit has

no effect.

bit 0 = over current
bit 1 = under current
bit 2 = over kVA
bit 3 = under kVA
bit 4 = over voltage
bit 5 = under voltage
bit 6 = phase loss A
bit 7 = phase loss B
bit 8 = phase loss C
bits 9-15 = 0

Phase Loss Threshold

Integer % of other phases

AV11

Percent

0

38

Phase Loss Threshold (0 to 100%, default = 65535): these

exist independently for all 3 phases (A, B, C). This register

sets the alarm threshold for all three phases. This setting

is the percent deviation of a phase from the average of

all 3 phases (register 8). The decision logic is constructed

so that normal power-ups do not trigger alarms. A phase

loss alarm will occur only if the following conditions are

met:

1. The average L-L voltage (register 8) is greater than 25V.
2. The L-N voltage on a phase (register 20, 21, or 22) is less

than the percent deviation set by this threshold.

3. This threshold is set between 0 and 100%.

H8238 Series Multi-Circuit Meters (H8238, H8238E & H8238EL), cont.

Advertising