Door lock connections, Internal power supply mode, A. connection for power-to-unlock type – V-Tech DMR18 Manual User Manual

Page 4: B. connection for power--off-to-unlock type

Advertising
background image

4. Door Lock Connections

1. Internal Power Supply Mode

Use the power of the system to supply for the electronic lock, so that the lock can be

connected to the door station directly, without an additional power supply for the electronic lock.

Note that the door station can only output 12Vdc power, therefore the kind of lock is limited.

• The rated power of the lock must be less than 12Vdc 300mA when using internal power

supply mode

• The GND must connect to the negative of the lock, and the COM connect to the positive .

• Jumper set to 1-2 position for Power-to-Unlock safety type(

Normally open mode

); set

to 2-3 position for Power-off-to -Unlock type(

Normally closed mode

).Note that the

unlock relay mode is set on the

Parameter

tab of DT CONFIG software.

• If different unlocking time is needed to be configured, the DT CONFIG software can be

used to change the

Unlock Timing

on the

Parameter

tab(see the program section).

JP_LK

12V 300mA

Jumper set to 1-2 position

+

-

+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -

1

2

3

set to Normally open on the

Unlock Relay mode on DT-config

software.

A. Connection for Power-to-Unlock type:

12V 300mA

Jumper set to 2-3 position

+12V
LK - (GND)
LK+(COM)
N.O.
EB+
EB -

+

-

set to Normally Closed on the

Unlock Relay mode on DT-config

software.

JP_LK

1

2

3

B. Connection for Power--off-to-Unlock type:

-3-