Installation, Multi-grain temperature sensor – Grain Systems PNEG-673 User Manual

Page 15

Advertising
background image

2000 Autoflow

15

Multi-Grain Temperature Sensor

1.

Remove the two wires attached to the grain tem-

perature sensor connected to terminal #22 and

terminal #23 in the fan control box.

2. Mount the four grain temperature sensor brack-

ets evenly around the drying chamber on out

side leveling band posts (figure 5).

3. With bin bolts mount the bracket so the sensor is

10.1/2” above the floor sheet rib.

on all temperature sensor brackets to exit the dry

ing chamber at the same place.

6. Run the cords back into the fan control box.

7. Wire the four temperature sensors into terminal

#22 and terminal #23 as detailed in Figure 4 and

the close up detail on page 17.

Figure 4: Illustration of the connection between the master heater control box and multiple sensors in the

drying chamber.

INSTALLATION

band post, and across the top leveling band.

5. Take the cords through the space between the roof

and the top sidewall sheet. There should be enough

4. Wire tie the cords so they feed up the leveling