In chart, Is reached, Are pro – Grain Systems PNEG-1856 User Manual

Page 2: Baldor motor kit

Advertising
background image

Page 2 of 9

PNEG-1856

Baldor Motor Kit

Programming Baldor H2 and VS Drives on Dryers Built 1993 and
Prior or 1998 and UP (Continued)

All parameters and their settings to be changed for Zimmerman purposes shown in chart

below

.

NOTE: After programming is complete if local is displayed in upper right hand corner of status screen.

Then Local/Remote button will have to be pressed to change to remote. This is a one time
operation and will not have to be done in the future.

* NOTE: Accutrol Unload Dryers Only - 5 amps is selected for 17' diameter dryers, 6 amps for

23'-4" diameter dryers. Dryers with metering augers stay at factory setting.

Top Level

Programming Menu

1

st

Level

Parameter Group

Individual

Parameters

Settings

Zimmerman Changes

Level 1 Blocks

Ramp Rates

Accel Time #1

3 Seconds

Decel Time #1

3 Seconds

Level 1 Blocks

Keypad Setup

Stop Key

OFF

Stop Mode

Coast

Run Forward

OFF

Run Reverse

OFF

Level 1 Blocks

Input Setup

Operating Mode

Standard Run 3 Wire

Command Source

Analog In1

Analog In1 Type

Potentiometer

Level 1 Blocks

Output Setup

Analog Out 1 Type

0-5V

Level 2 Blocks

Drive Limits

Minimum Output Speed

7 Hertz

Maximum Output Speed

75 Hertz

Level 2 Blocks

Drive Protect

External Trip

ON

Level 2 Blocks

Motor Data

Motor Rated Amps

Factory/5 Amps or 6 Amps*

Press R to Exit

Press R to Exit

Press R to Exit

Press ENTER at Status