PNEG-1856

Baldor Motor Kit

Programming Baldor H2 and VS Drives on Dryers Built
1994-1997 (Continued)

All parameters and their settings to be changed for Zimmerman purposes shown in chart

below

.

NOTE: After programming is complete if local is displayed in upper right hand corner of status screen.

Then Local/Remote button will have to be pressed to change to remote. This is a one time
operation and will not have to be done in the future.

* NOTE: Accutrol Unload Dryers Only - 5 amps is selected for 17' diameter dryers, 6 amps for

23'-4" diameter dryers. Dryers with metering augers stay at factory setting.

Top Level

Programming Menu

1

st

Level

Parameter Group

Individual

Parameters

Settings

Zimmerman Changes

Level 1 Blocks

Ramp Rates

Accel Time #1

3 Seconds

Decel Time #1

3 Seconds

Level 1 Blocks

Keypad Setup

Stop Key

OFF

Stop Mode

Coast

Run Forward

OFF

Run Reverse

OFF

Level 1 Blocks

Input Setup

Operating Mode

Standard Run 3 Wire

Command Source

Analog In2

Analog In2 Type

0-5V

Level 1 Blocks

Output Setup

Analog Out 1 Type

0-5V

Level 2 Blocks

Drive Limits

Minimum Output Speed

7 Hertz

Maximum Output Speed

75 Hertz

Level 2 Blocks

Drive Protect

External Trip

ON

Level 2 Blocks

Motor Data

Motor Rated Amps

Factory/5 Amps or 6 Amps*

Press R to Exit

Press R to Exit

Press R to Exit

Press ENTER at Status