Fan specifications, Chapter 4 fan specifications, 1750 rpm fan electrical specifications – Grain Systems PNEG-163-08 User Manual

Page 18: Pecifications chart

Advertising
background image

18

PNEG-163-08 Centrifugal Fan

4. Fan Specifications

1750 RPM Fan Electrical Specifications

IMPORTANT: The values listed in this chart are recommendations only. Electrical installation must

be performed by a qualified electrician, in accordance with National and Local Electrical
Codes. Any violation of electrical wiring codes could jeopardize the warranty.

Fan Horsepower

3

5

7-1/2

10

Phase

1

3

1

3

1

3

1

3

Volts

230

230

460

575

230

230

460

575

230

230

460

575

230

230

460

575

Full Load Current (Amps) *

17

9.6

4.8

3.9

28

15.2

7.6

6.1

40

22

11

9

50

28

14

11

Minimum Wire Size

Copper Wire

Copper Wire

Copper Wire

Copper Wire

50' Run

12

14

14

14

10

14

14

14

8

10

14

14

6

10

14

14

100' Run

12

14

14

14

8

12

14

14

8

10

14

14

6

10

14

14

200' Run

8

12

14

14

6

10

14

14

4

8

14

14

4

6

12

14

300' Run

6

10

14

14

4

8

14

14

3

6

12

14

2

4

10

12

Minimum Wire Size

Aluminum Wire

Aluminum Wire

Aluminum Wire

Aluminum Wire

50' Run

10

12

12

12

8

12

12

12

6

10

12

12

4

8

12

12

100' Run

8

12

12

12

6

10

12

12

6

8

12

12

4

8

12

12

200' Run

6

10

12

12

4

8

12

12

3

6

12

12

2

4

10

12

300' Run

4

8

12

12

3

6

12

12

1

4

10

12

0

3

8

10

Fuse Size (Slow Blow)

30

15

8

6

50

25

12

10

70

40

20

15

90

45

25

20

Breaker Size

50

15

15

15

70

30

15

15

100

40

20

15

125

50

30

20

* Based on NEC Tables 430-148 and 430-150

Fan Horsepower

15

20

25

30

40

50

Phase

1

3

3

3

3

3

3

Volts

230

230

460

575

230

460

575

230

460

575

230

460

575

230

460

575

230

460

575

Full Load Current (Amps) * 65

42

21

17

54

27

22

68

34

27

80

40

32

104

52

41

130

65

52

Minimum Wire Size

Copper Wire

Copper Wire

Copper Wire

Copper Wire

Copper Wire

Copper Wire

50' Run

4

6

10

12

4

10

10

4

8

10

3

8

8

1

6

6

00

4

6

100' Run

4

6

10

12

4

10

10

4

8

10

3

8

8

1

6

6

00

4

6

200' Run

3

4

10

12

4

10

10

3

8

10

3

8

8

1

6

6

00

4

6

300' Run

1

4

10

10

3

8

10

2

6

8

1

6

8

0

6

6

00

4

6

Minimum Wire Size

Aluminum Wire

Aluminum Wire

Aluminum Wire

Aluminum Wire

Aluminum Wire

Aluminum Wire

50' Run

2

4

10

10

3

8

10

2

6

8

1

6

8

00

4

4

0000

2

4

100' Run

2

4

10

10

3

8

10

2

6

8

1

6

8

00

4

4

0000

2

4

200' Run

1

3

8

10

2

8

10

1

6

8

0

6

8

00

4

4

0000

2

4

300' Run

00

1

6

8

0

6

8

00

4

6

00

4

6

000

4

4

0000

2

4

Fuse Size (Slow Blow)

125

70

40

30

90

45

40

110

60

45

125

60

50

175

80

70

200

100

80

Breaker Size

175

70

40

30

90

50

40

110

60

50

125

60

50

175

80

70

200

100

80

* Based on NEC Tables 430-148 and 430-150