3. Installation

18

PNEG-634 2000 Top Dry Fan/Heater

Plenum Temperature Sensor

The plenum temperature sensor is the small grey PVC junction box attached by a cord to the fan/heater
control box on the master fan/heater unit.

1. On the right side of the far right fan/heater, drill one 3/4" hole even with the fan/heater unit in a valley

on the bin sidewall.

2. Insert the probe through the 3/4" hole.

3. Position the housing so the cord exits the housing horizontally and the tabs fall on the

sidewall peaks.

4. Use two (2) self-drilling screws to mount the housing to the bin sidewall.

5. Caulk between the housing and the sidewall to seal the gaps.

IMPORTANT: If the Top Dry is a 2 fan unit, do not mount the plenum temperature sensor between the

two (2) fan/heater units.

Figure 3J Plenum temperature sensor on the bin sidewall.