12-Channel/8-Channel, Flash-Configurable System

Managers with Nonvolatile Fault Registers

MAX16065/MAX16066

______________________________________________________________________________________ 13

of the EN comparator output or the software enable bit.
If operating in latch-on fault mode, toggle EN or toggle
the Software Enable bit to clear the latch condition and
restart the device once the fault condition has been
removed.
To initiate secondary sequencing and monitoring set the
software enable r73h[1] bit to 1. Additionally, if GPIO_ is
configured as EN2 then both the software enable 2 bit and
EN2 must be high. To power-down and disable monitor-
ing, either drive EN2 low or set the Software Enable2 bit to
‘0.’ See Table 2 for the software enable bit configurations.
When a fault condition occurs during the power-up cycle,
the EN_OUT_ outputs are powered down immediately,
independent of the state of EN2. Drive EN2 low to begin
the secondary power-down sequence. When EN2 is driv-

en high during the power-down sequence, the sequence
state machine continues the power-down sequence until
the secondary channels are powered off and then the
device immediately begins the power-up sequence.

Monitoring Inputs While Sequencing

An enabled MON_ input can be assigned to a slot
ranging from Slot 1 to Slot 12. EN_OUT_s are always
asserted at the beginning of a slot. The supply volt-
ages connected to the MON_ inputs must exceed the
undervoltage threshold before the programmed timeout
period expires otherwise a fault condition will occur. The
undervoltage threshold checking cannot be disabled
during power-up and power-down. See Tables 5 and
6 for the MON_ slot assignment bits. The programmed

Table

2. Software Enable Configurations

Table

3. Slot Delay Register

REGISTER

ADDRESS

FLASH

ADDRESS

BIT RANGE

DESCRIPTION

73h

273h

[0]

Software enable 1 (primary sequence)

[1]

Software enable 2 (secondary sequence)

[2]

1 = Margin mode enabled

[3]

Early warning threshold select
0 = Early warning is undervoltage
1 = Early warning is overvoltage

[4]

Independent watchdog mode enable
1 = Watchdog timer is independent of sequencer
0 = Watchdog timer boots after sequence completes

REGISTER

ADDRESS

FLASH

ADDRESS

BIT RANGE

DESCRIPTION

77h

277h

[3:0]

Sequence Slot 0 Delay

[7:4]

Sequence Slot 1 Delay

78h

278h

[3:0]

Sequence Slot 2 Delay

[7:4]

Sequence Slot 3 Delay

79h

279h

[3:0]

Sequence Slot 4 Delay

[7:4]

Sequence Slot 5 Delay

7Ah

27Ah

[3:0]

Sequence Slot 6 Delay

[7:4]

Sequence Slot 7 Delay

7Bh

27Bh

[3:0]

Sequence Slot 8 Delay

[7:4]

Sequence Slot 9 Delay

7Ch

27Ch

[3:0]

Sequence Slot 10 Delay

[7:4]

Sequence Slot 11 Delay

7Dh

27Dh

[3:0]

Sequence Slot 12 Delay

[7:4]

Grouped Sequence Split Location, Final Slot of Primary Sequence