R&M Materials Handling VARIABLE SPEED CONTROLS ControlMaster Plus Service Manual User Manual

Page 57

Advertising
background image

R&M Materials Handling, Inc.

4501 Gateway Boulevard

Springfield, Ohio 45502

P.: (937) 328-5100

FAX: (937) 325-5319

57/83

R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.

• S3 = Both EA+/- and EB+/- are missing
• S4 = EA+/- and EB+/- are crossconnected

S5 = SSU-board is missing or system load is
too high

• Encoder type and pulse number

F44

Device changed Option board or control unit has been

changed to different type or different power
rating

Reset the fault. Option board parameters or all parameters
are set up to default values.

X

F45

Device added

Option board of different type or drive of
different power rating added.

Reset the fault. Option board parameters or all parameters
are set up to default values.

X

F50

Reference
value fault

Analog input signal is out of selected range
1-9V or 2-10V
• Control cable is broken
• Signal source has failed

Check:
• Reference cable
• Reference source

X

F 51 Stop limit

Stop limit has tripped

Reset: keep controller at zero >300ms.

Ensure that fault disappears after leaving the stop limit.

X

F 55 Board Fault

Some of following board is missing:
• A = Basic I/O board
• B = Thermistor board
• D = Expansion board

Reset: switch power off and restart after the lamps of
keypad are off.

Check:
• board slots A, B and D
• drive selection
• control mode

X

F 56 Generator side

current limit

Too short deceleration time
• generator side current limit

Reset has an additional 5 s time delay.

Check:
• deceleration time

X

F 57

Thermistor fault Thermistor input in relay / thermistor board

has detected motor overtemperature. Fault
appears when thermistor input has been
open over 1s.

Check:
• motor cooling and loading
• thermistor connection. If expansion board thermistor

input is not used, it should be shorted

• motor parameters
• the brake operation

X

F 60 Parameter fault Inverter has lost parameters. Drive selection

parameter has changed to 0 / none.

Download parameters from keypad

X

F 61

Overspeed Fault

SSU has tripped to Overspeed (hardware
supervision). Motor speed has increased
above overspeed detection level.

Reset: switch power off and restart after the lamps of
keypad are off.

Check:

function and cabling

maximum frequency setting parameters

SSU settings

X

F 62

Speed Difference
Fault

SSU has tripped to Speed Difference

Reset: switch power off and restart after the lamps of
keypad are off.

Check:

pulse sensor/encoder function and cabling

pulse sensor/encoder pulse number

speed difference supervision settings

X

F 63

Stall Supervision
Fault

SSU has tripped to Stall.

Reset: switch power off and restart after the lamps of
keypad are off.

Check:

brake operation

pulse sensor/encoder function and cabling

stall supervision settings

X

F 64

SSU Relay Test
Fault

Relay in SSU board is damaged or SSU
relay is bypassed

Reset: switch power off and restart after the lamps of
keypad are off.

Check:

ES and RDY external connections

OK input operation

change SSU board

X

F 65

SSU Watchdog

SSU internal fault

interference fault between SSU board and
control board

component failure (control board or SSU
board)

Reset: switch power off and restart after the lamps of
display are off.

Check:

SSU status (System menu / System info / Expander
boards / C: SSU / status)

SSU LED’s

If the fault comes again, contact service

X

F 66

SSU Overspeed
Limit

SSU overspeed limit has been set over
140% of maximum frequency

Check:

set SSU overspeed limit under 140% of maximum
frequency

X