OSRAM PD BASIC User Manual

Dali ls/pd basic, Light and motion sensor fitting instructions, Installation

Advertising
background image

Page 1 of 2

Light and motion sensor

Fitting instructions

DALI LS/PD BASIC

Vcc LS 0V

NC

PD

NC

OSRAM

DALI LS/PD

BASIC

D

C

C

B

A

D

Description

Purpose and application

The DALI LS/PD BASIC sensor detects the presence of per-

sons and measures the intensity of ambient light.
The sensor is designed for connection to DALI RC BASIC SO

control units and can be installed in luminaires or ceilings.

Function

The sensor measures the brightness in the area requiring

control and transmits the light value to the control unit for the

purpose of keeping it to an adjustable set value by introducing

artificial light according to the amount of daylight available. As

the amount of daylight increases, artificial lighting is reduced.
The sensor always transmits the detection of movements of

persons to the control unit. After the sensor stops detecting

motion, the control unit switches the luminaires off following an

adjustable delay period.

Design

The sensor is made up of the following components:
• Light sensor (A)
• Motion sensor (B)
• Connections (C):

– Supply voltage (Vcc)

– Ground (0V)

– Output for light measurement value (LS)

– Output for motion signal (PD)

• Housing (D)

Installation

Safety instructions

The sensor must only be installed and put into operation by

a qualified electrician. The applicable safety regulations and

accident prevention regulations must be observed.

WARNING!
Exposed, live cables or damaged

housing.
Danger of electric shock!
• Only work on the sensor when it is

de-energised.

CAUTION!

Destruction of the sensor and other devices through

incorrect mounting!
• Adhere to the connection diagram.
• Do not exceed the maximum line length.
• When mounting in luminaires, use a UV-resistant

cable.

• Do not route the sensor lines together with DALI

or power supply lines.

• Only connect the sensor to control units of type

DALI BASIC SO.

Attaching the sensor to the

fluorescent lamps

Precondition: T5 or T8 lamps with a min. grid of 60 mm.



Determining a suitable installation location (see „Selecting

the installation location“)

‚

Insert the lamp clip into the sensor housing base.

ƒ

Attach the sensor to the lamp end with the lamp clip to avoid

weighing down the lamp excessively. Minimum distance to

the lampholder due to heat development of the coils: 8 cm.

„

If necessary, adjust the sensor installation depth to the depth

of the grid luminaire by sliding the lamp clip in or out.

…

Pull the sensor off of the attached housing base.

†

Connect the sensor; see the connection diagram.

‡

Attach the sensor to the housing base again.

Attaching the sensor to the ceiling



Determining a suitable installation location (see „Selecting

the installation location“).

‚

Take off the sensor base plate.

ƒ

Screw the base plate onto the ceiling.

„

Connect the sensor; see the connection diagram.

…

Attach the sensor to the base plate.

Advertising