Page 14

Advertising
background image

3.2 Configure the Master

3.2.1 EDS File

A large part of the system configuration is the setting of application related parameters. EDS (Electronic Data Sheet) files simplify the setting up of most of the
DeviceNet configurable parameters. GE provides a generic English EDS file covering all voltage and power sizes, for off-line configuration. The EDS file can be
downloaded from http://www.geelectrical.com/drives.

NB!
The EDS-file does not contain all parameters but a selected, limited number of parameters with generic minimum, maximum and default values.

3.3 Configure the Frequency Converter

3.3.1 Frequency Converter Parameters

Pay particular attention to the following parameters when configuring the frequency converter with a DeviceNet interface. Please refer to the Parameters chapter
for more details of each parameter.

par. K-40 [Hand] Button on Keypad.
If the Hand button on the frequency converter is activated, control of the drive via the DeviceNet interface is disabled. After initial power-up the frequency
converter will automatically detect whether a fieldbus option is installed in slot A, and set par. O-02 Control Word Source to [Option A]. If an option is
added to, changed in or removed from an already commissioned drive, it will not change par. O-02 Control Word Source but will enter Trip Mode, and
the frequency converter will display an error.

par. O-10 Control Word Profile (see section How to Control the Frequency Converter). Choose between the GE Drive Profile and the ODVA profile. Select
the desired DeviceNet instance in par. DN-10 Process Data Type Selection.

par. O-50 Coasting Select to par. O-56 Preset Reference Select (see section Parameters). Selection of how to gate the DeviceNet control commands with
digital input command of the control card.

NB!
When par. O-01 Control Site is set to [2] Control word only, then the settings in par. O-50 Coasting Select to par. O-56 Preset Reference Select will be overruled,
and will all act on Bus-control

par. O-03 Control Word Timeout Time to par. O-05 End-of-Timeout Function. The reaction in the event of a bus time out is set via these parameters

par. DN-10 Process Data Type Selection. Default is 125 kbps.

par. DN-02 MAC ID. Default is 63.

3.3.2 LEDs

The DeviceNet control card contains two bi-colour (green/red) LEDs for each connector hook-up port, to indicate the state of the device and the network respec-
tively. For details of the range of communications status indicated by the LEDs, please refer to the Troubleshooting chapter.

AF-600FP /650 GP DeviceNet Operating Instructions